Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
73
SERVICE
MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MINIMUM
MAXIMUM
10 Gates Closed %
2
0
5
11 GP Sig Filter TC
0.01
0.001
5
11 GATE LIMIT
01 Gate Limit
Monitor
04 Gate Limit Coinc.
Monitor
03 Analog In Limit All Time
FALSE
FALSE
TRUE
04 Analog In @ 4 mA
0
0
100
05 Analog In @ 20 mA
100
0
100
06 Breakaway GL
30
0
100
07 Hold@Brkawy Time
1
0.001
30
08 Speed-no-Load GL
15
0
100
09 Prepos Online Gate Lim
100
0
100
10 Auto Raise Delay
120
0
600
11 Auto Raise Rate
0.5
0.01
100
12 Man R/L Ramp Rate
2
0.01
100
12 VALVE DRIVER (I)
01 Actuator Demand
Monitor
02 Valve Offset
0
-100
100
03 Offline Valve Gain
1
0
50
04 Online Valve Gain
1
0
50
05 Dither Frequency
2
1
5
06 Dither Frequency
Monitor
07 Dither Amplitude
0
0
100
13 VALVE DRIVER (P)
01 Actuator Demand
Monitor
14 MANUAL AND MAINT
01 Manual Mode Enabled
Monitor
02 Enable Maint Mode
FALSE
FALSE
TRUE
03 Preset Value
0
-10
110
04 GoTo Preset Value
FALSE
FALSE
TRUE
15 OFFLIN/ISOCH CTRL
01 Offline/Isoch Ref
Monitor
02 I’m in Control
Monitor
03 PID Output
Monitor
04 Raise/Lower Rate
0.01
0.001
100
05 Speed-no-Load Ref
100.05
75
125
06 Upper Limit
– Ref
110
75
250
07 Lower Limit
– Ref
20
0
100
08 Enable SDR Invers
TRUE
FALSE
TRUE
09 PID Clamp Win +/-
4
0
5
16 ONLIN/DROOP CTRL
01 Speed Adjust
Monitor
02 I’m in Control
Monitor
03 Gate Pos Setpoint
Monitor
04 PID Output
Monitor
05 Raise/Lower Rate
0.1
0
1000
06 Setpoint Deriv TC
0.96
0.001
5
07 PID Clamp Win +/-
4
0
5