Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
69
CONFIGURE
MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MINIMUM
MAXIMUM
10 Use DI4 NC?
FALSE
FALSE
TRUE
11 Use DI5 NC?
FALSE
FALSE
TRUE
12 Use DI6 NC?
FALSE
FALSE
TRUE
13 Use DI7 NC?
FALSE
FALSE
TRUE
14 Use DI8 NC?
FALSE
FALSE
TRUE
06 CONFIG DIGITAL OUT
01 Config Relay #2
1
1
25
02 Relay #2 Function
Monitor
03 Config Relay #3
1
1
25
04 Relay #3 Function
Monitor
05 Config Relay #4
1
1
25
06 Relay #4 Function
Monitor
07 CONFIG ANALOG OUT
01 Config AO#1
2
1
11
02 AO#1 Function
Monitor
03 AO#1 Current Output
Monitor
07A CONFIG AN OUT LINKNET
01 Config AO#1
1
1
11
02 AO#1 Function
Monitor
03 AO#1 Current Output
Monitor
04 Config AO#2
1
1
11
05 AO#2 Function
Monitor
06 AO#2 Current Output
Monitor
08 CONFIG LEVEL CTRL
01 Minimum Elevation
4
-30000
30000
02 Maximum Elevation
20
-30000
30000
03 1=Head / 2=Tail
1
1
2
04 Config Setpoint
1
1
2
05 Fix Spd in Level?
FALSE
FALSE
TRUE
09 CONFIG MODBUS
01 Network Address RS-422
1
1
247
02 1=ASCII / 2=RTU RS-422
2
1
2
03 Timeout (sec) RS-422
1
0.5
30
04 Network Address RS-232
1
1
247
05 1=ASCII / 2=RTU RS-232
2
1
2
06 Timeout (sec) RS-232
1
0.5
30
10 CONFIG SYNC LOAD CONTROL
01 Synchronize Only?
TRUE
FALSE
TRUE
02 Sig Type
– 2=An / 3=Dig
1
1
3
Released