Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
75
SERVICE
MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MINIMUM
MAXIMUM
03 Step Value (%)
3
-10
10
04 Negative Step?
FALSE
FALSE
TRUE
23 BRAKE
01 Brake Perms Met
Monitor
02 Brake Enable Spd
50
0
100
03 Brake Enable Gpos
2
0
100
04 Brake on Timer
60
0
10000
05 Brake on Pulse Time
15
0
10000
06 Brake off Pulse Time
10
0
10000
24 CREEP
01 Unit Creeping?
Monitor
02 Creep Speed (%)
5
0
10
03 Dead Stop (sec)
60
10
600
04 Reset Creep (sec)
5
0
600
05 Look Again (sec)
5
0
600
25 MODBUS
01 Baud Rate
6
1
7
02 Stop Bits
1
1
3
03 Parity Bits
1
1
3
04 Bits
2
1
2
05 Driver
1
1
2
06 Freeze Remote Setpoint
FALSE
FALSE
TRUE
07 Freeze Remote Init Bsld Ref
FALSE
FALSE
TRUE
08 Freeze Baseload Ref
FALSE
FALSE
TRUE
09 Freeze Level Ref
FALSE
FALSE
TRUE
10 Freeze Stroke Actuator
FALSE
FALSE
TRUE
11 Freeze Baseload Ref - Rem
FALSE
FALSE
TRUE
12 Choose Modbus Comm
FALSE
FALSE
TRUE
26 SYNCHRONIZE
01 Speed Bias
Monitor
02 Speed Bias Analog Gain
1
0.001
100
03 Spd Bias An Sig Filtr TC
0.01
0.001
3
04 Speed Bias Digital Rate
0.1
0.01
1
27 CONFIG SPD SW
01 SW1
– Decreasing?
FALSE
FALSE
TRUE
02 Spd SW1
– Hi Set
100
0
200
03 Spd SW1
– Hi Delay
0
0
600
04 Spd SW1
– Low Set
98
0
200
05 Spd SW1
– Low Delay
0
0
600
06 SW2
– Decreasing?
FALSE
FALSE
TRUE
07 Spd SW2
– Hi Set
100
0
200
08 Spd SW2
– Hi Delay
0
0
600
09 Spd SW2
– Low Set
98
0
200
10 Spd SW2
– Low Delay
0
0
600
11 SW3
– Decreasing?
FALSE
FALSE
TRUE
12 Spd SW3
– Hi Set
100
0
200
13 Spd SW3
– Hi Delay
0
0
600
14 Spd SW3
– Low Set
98
0
200
15 Spd SW3
– Low Delay
0
0
600
Released