Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
77
SERVICE
MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MINIMUM
MAXIMUM
09 Baseload Lower Time (sec)
60
1
600
10 Rmt Bsload Inc Time (sec)
60
1
600
11 Rmt Bsload Dec Time (sec)
60
1
600
12 Breaker Open Time (sec)
1
0.8
6
13 Ramp @ Min, CB Delay (sec)
5
1
10
33 BSLD CTRL (PID & MONITOR)
01 Baseload Reference (kW)
Monitor
02 Generator Load (kW)
Monitor
03 Baseload Reference (%)
Monitor
04 Generator Load (%)
Monitor
05 Baseload PID Output (%)
Monitor
06 Bsld Proportional Gain
0.7
0
100
07 Bsld Integral Gain
0.2
0
10
08 Baseload Speed Ramp Rate
0.2
0
100
Released