Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
43
4 = 75% 16 mA
15 mA
150 mA
5 = 100% 20 mA
20 mA
200 mA
6 = Manually controlled analog value
07 MANUAL ACTUATOR VALUE:
[*0 (-10,110)] This menu item can be adjusted to any value between -
10% and 110% of full scale. If the previous menu item, “SELECT ACTUATOR OUT,” is tuned to 6, then
this number is used to control the actuator output. This parameter is only used when the Calibrate Mode
is enabled via Watch Window. If the Calibration Mode is enabled via Modbus then the actuator stroke can
only be performed via Modbus.
04A CAL AN OUT LINKNET
This menu allows you to force the analog outputs of the LINKnet HT module to any value.
The Calibrate Mode should only be entered when the unit is shut
down, de-watered, and it is safe to move the gates. All I/O points will
be under complete manual control!
01 CALIBRATE ENABLED:
[MONITOR]
This item displays if the calibrate mode is enabled.
02 FORCED AN OUT #1:
[MONITOR] This menu item displays the value (in percent of full scale range)
that the analog output are being forced to. For example, if this menu item is displaying 25, then analog
output will be 8 mA (25% of 16 mA plus 4 mA).
03 SELECT ANALOG OUT #1:
[*1 (1,6)] This menu item selects the output current %. The integer can
be set to any of the following:
4
–20 mA 0–20 mA
0
–200 mA
1 = 0% 4 mA
0 mA
0 mA
2 = 25% 8 mA
5 mA
50 mA
3 = 50% 12 mA
10 mA
100 mA
4 = 75% 16 mA
15 mA
150 mA
5 = 100% 20 mA
20 mA
200 mA
6 = Manually controlled analog value
04 MANUAL AO#1 VALUE:
[*0 (-10,110)] This menu item can be adjusted to any value between -10%
and 110% of full scale. If the previous menu item, “SELECT ANALOG OUT,” is tuned to 6, then this
number is used to control the analog output.
05 FORCED AN OUT #2:
[MONITOR] This menu item displays the value (in percent of full scale range)
that the analog output are being forced to. For example, if this menu item is displaying 25, then analog
output will be 8 mA (25% of 16 mA plus 4 mA).
06 SELECT ANALOG OUT #2:
[*1 (1,6)] This menu item selects the output current %. The integer can
be set to any of the following:
4
–20 mA 0–20 mA
0
–200 mA
1 = 0% 4 mA
0 mA
0 mA
2 = 25% 8 mA
5 mA
50 mA
3 = 50% 12 mA
10 mA
100 mA
4 = 75% 16 mA
15 mA
150 mA
5 = 100% 20 mA
20 mA
200 mA
6 = Manually controlled analog value
07 MANUAL AO#2 VALUE:
[*0 (-10,110)] This menu item can be adjusted to any value between -10%
and 110% of full scale. If the previous menu item, “SELECT ANALOG OUT,” is tuned to 6, then this
number is used to control the analog output.
05 CAL DISCRETE INs
This menu allows you to monitor the condition of all discrete inputs. When any of these menu items
display TRUE, the contacts for that discrete input are closed.
Released