Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
40
05 1=ASCII / 2=RTU RS-232:
[*2 (1,2)] This integer selects the format of the communication. If the value
is tuned to 1, the Modbus will communicate in ASCII format. If the value is tuned to 2, the Modbus will
communicate in RTU (Remote Terminal Unit) format.
06 TIMEOUT (sec) RS-232:
[*10 (0.5,30)] This value is the number of seconds the 2301E-HT will wait
before it results in an Exception or Link Error.
10 CONFIG SYNC_LOAD CONTROL
This menu needs to be configured if a speed bias bias signal is going to be used in the control.
01 SYNCHRONIZE ONLY?:
[TRUE or *FALSE] If the Synchronizer/Load Control is only going to be used
to synchronize the unit, then this value should be set to TRUE.
02 SIG TYPE
– 2=AN / 3=DIG:
[*1 (1,3)] If the speed bias signal source is coming from an analog input
this variable must be configured to 2. In this case an analog input must be configured as a speed bias
input. If the speed bias signal source is coming from digital inputs this variable must be configured to 3. In
this case two digital inputs must be configured, one for speed bias raise and another for speed bias lower.
A value 1 says that neither analog nor digital inputs are going to be programmed for speed bias function.
Service Menu Descriptions
01 MONITOR ALARMS
This menu displays all governor alarms and the current condition. A TRUE indication next to any alarm
indicates the alarm condition is present, and a FALSE indicates the alarm condition is not present.
01 GOVERNOR RESET:
[TRUE or *FALSE]. This value can be tuned TRUE and then back to FALSE to
reset the 2301E-HT digital control.
02 GOVERNOR ALARM:
[MONITOR]
03 LEVEL SIGNAL FAIL:
[MONITOR]
04 REM REF SIG FAIL:
[MONITOR]
05 SPEED BIAS SIG FAIL:
[MONITOR]
06 SM GATE MISMATCH:
[MONITOR]
07 MODBUS LINK ERROR:
[MONITOR]
08 DIRTY OIL SWITCH:
[MONITOR]
09 GOVERNOR SHUTDOWN:
[MONITOR]
10 CREEP DETECTED:
[MONITOR]
11 BREAKER OPEN TIME EXCEED:
[MONITOR]
12 BASE LOAD REF SIG FAIL:
[MONITOR]
13 GATE LIMIT SIG FAIL:
[MONITOR]
14 RMT LEVEL REF SIG FAIL:
[MONITOR]
15 SPEED SIGNAL MPU#1 FAIL:
[MONITOR]
16 SPEED SIGNAL MPU#2 FAIL:
[MONITOR]
17 AIO LINKNET COMM ALARM:
[MONITOR]
18 AIO LINKNET TEMP ALARM:
[MONITOR]
02 MONITOR SHUTDOWNS
This menu displays all governor shutdowns and the current condition. A TRUE indication next to any
alarm indicates the shutdown condition is present, and a FALSE indicates the shutdown condition is not
present
01 GOVERNOR RESET:
[TRUE or *FALSE]. This value can be tuned TRUE and then back to FALSE to
reset the 2301E-HT digital control.
02 GOVERNOR SHUTDOWN:
[MONITOR]
03 FIRST SHUTDOWN:
[MONITOR]. This value shows the first shutdown that is active according to the
table below:
0- NO SHUTDOWNS
1- SPEED SIGNAL FAILURE (ALL)
2- OVERSPEED
3- GROSS GATE MISMATCH
Released