Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
44
01 DI #1(A) RUN/STOP:
[MONITOR]
02 DI #2(B) RAISE:
[MONITOR]
03 DI #3(C) LOWER:
[MONITOR]
04 DI #4(D) BREAKER:
[MONITOR]
05 DI #5(E) EMERGENCY SHUTDOWN:
[MONITOR]
06 DI #6(F) CONFIG 1:
[MONITOR]
07 DI #7(G) CONFIG 2:
[MONITOR]
08 DI #8(H) CONFIG 3:
[MONITOR]
06 CAL RELAY OUTPUTS
This menu allows you to manually energize each relay individually. This menu allows you to manually
energize each relay individually. When the any of the following menu items are tune to TRUE, the
corresponding relay or LED will be energized.
01 CALIBRATE ENABLED:
[MONITOR]
This item displays if the calibrate mode is enabled
02 FORCE RELAY OUT 1:
[TRUE or *FALSE]
03 FORCE RELAY OUT 2:
[TRUE or *FALSE]
04 FORCE RELAY OUT 3:
[TRUE or *FALSE]
05 FORCE RELAY OUT 4:
[TRUE or *FALSE]
06 USE DO#1 NC?
: Select TRUE if you want digital output #1 normally closed or leave FALSE if you
want normally open
07 USE DO#2 NC?
: Select TRUE if you want digital output #2 normally closed or leave FALSE if you
want normally open
08 USE DO#3 NC?
: Select TRUE if you want digital output #3 normally closed or leave FALSE if you
want normally open
09 USE DO#4 NC?
: Select TRUE if you want digital output #1 normally closed or leave FALSE if you
want normally open
07 CONFIG ANALOG OUT
This menu allows you to define the scale of the analog output.
01 - ANALOG OUT #1 FUNCTION:
[MONITOR] The user can see the programmed function for the
analog output #1.
02 AO1 LOW LIM VAL=
:[*0(-30000,30000)] Configure the low value of this analog output (4 mA)
03 AO1 HIGH LIM VAL=
:[*0(-30000,30000)] Configure the high value of this analog output (20 mA)
07A CONFIG AN OUT LINKNET
This menu allows you to define the scale of the analog outputs for the LINKnet HT module.
01 - ANALOG OUT #1 FUNCTION:
[MONITOR] The user can see the programmed function for the
analog output #1.
02 AO1 LOW LIM VAL=
:[*0(-30000,30000)] Configure the low value of this analog output (4 mA)
03 AO1 HIGH LIM VAL=
:[*0(-30000,30000)] Configure the high value of this analog output (20 mA)
04 - ANALOG OUT #2 FUNCTION:
[MONITOR] The user can see the programmed function for the
analog output #2.
05 AO2 LOW LIM VAL=
:[*0(-30000,30000)] Configure the low value of this analog output (4 mA)
06 AO2 HIGH LIM VAL=
:[*0(-30000,30000)] Configure the high value of this analog output (20 mA)
08 MAIN CONTROL
The main unit controls are available in this menu.
01 GOVERNOR RUN:
[MONITOR] This menu item monitors the RUN/STOP state of the control. When
TRUE, the unit is in RUN mode, when FALSE, the unit is in STOP mode.
02 UNIT ONLINE:
[MONITOR] This menu item monitors the generator breaker’s status. TRUE indicates
that the unit is ONLINE (generator breaker is closed), and FALSE indicates that the unit is OFFLINE
(generator breaker is open).
03 START GATE RATE:
[*1 (0.01,100)] This is the rate at which the gate limit ramps from the
“Breakaway” gate limit to the “Speed-No-Load” gate limit during startup. The rate is gate position
percent/second.