04 SPD SW1 - LOW SET:
[*98.0 (0.0,200.0)] This is the low % of rated set point for the speed switch.
When the switch is increasing, this set point is the reset point of the speed switch. When the switch is
decreasing, this set point is the trip point of the speed switch.
05 SPD SW1 - LO DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the speed should be less
than LO SET to de-energize the relay when configured to Increasing or to energize the relay when
configured to decreasing.
06 SW2 - DECREASING?:
[TRUE or *FALSE] This determines if Speed Switch #2 is an increasing
switch or a decreasing switch. If the switch should trigger when the unit is slowing down, then this value
should be set to TRUE. If the switch should trigger when the unit is speeding up, then this value should
be set to FALSE.
07 SPD SW2 - HI SET:
[*100.0 (0.0,200.0)] This is the high % of rated set point for the speed switch.
When the switch is increasing, this set point is the trip point of the speed switch. When the switch is
decreasing, this set point is the reset point of the speed switch.
08 SPD SW2 - HI DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the speed should be
greater than HI SET to energize the relay when configured to Increasing or to de-energize the relay when
configured to decreasing.
09 SPD SW2 - LOW SET:
[*98.0 (0.0,200.0)] This is the low % of rated set point for the speed switch.
When the switch is increasing, this set point is the reset point of the speed switch. When the switch is
decreasing, this set point is the trip point of the speed switch.
10 SPD SW2 - LO DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the speed should be less
than LO SET to de-energize the relay when configured to Increasing or to energize the relay when
configured to decreasing.
11 SW3 - DECREASING?:
[TRUE or *FALSE] This determines if Speed Switch #3 is an increasing
switch or a decreasing switch. If the switch should trigger when the unit is slowing down, then this value
should be set to TRUE. If the switch should trigger when the unit is speeding up, then this value should
be set to FALSE.
12 SPD SW3 - HI SET:
[*100.0 (0.0,200.0)] This is the high % of rated set point for the speed switch.
When the switch is increasing, this set point is the trip point of the speed switch. When the switch is
decreasing, this set point is the reset point of the speed switch.
13 SPD SW3 - HI DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the speed should be
greater than HI SET to energize the relay when configured to Increasing or to de-energize the relay when
configured to decreasing.
14 SPD SW3 - LOW SET:
[*98.0 (0.0,200.0)] This is the low % of rated set point for the speed switch.
When the switch is increasing, this set point is the reset point of the speed switch. When the switch is
decreasing, this set point is the trip point of the speed switch.
15 SPD SW3 - LO DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the speed should be less
than LO SET to de-energize the relay when configured to Increasing or to energize the relay when
configured to decreasing.
28 CONFIG GP SW
If any relay output is configured as gate position switch, then the gate position switches are configured
here. If no relay outputs are configured as gate position switches, then this menu does not affect the
control and can be skipped.
01 SW1 - DECREASING?:
[TRUE or *FALSE] This determines if Gate Position Switch #1 is an
increasing switch or a decreasing switch. If the switch should trigger when the gates are closing, then this
value should be set to TRUE. If the switch should trigger when the gates are opening, then this value
should be set to FALSE.
02 GP SW1 - HI SET:
[*50 (0.0,100.0)] This is the high set point for the gate position switch. When the
switch is increasing, this set point is the trip point of the gate position switch. When the switch is
decreasing, this set point is the reset point of the gate position switch.
03 GP SW1 - HI DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the gate position should be
greater than HI SET to energize the relay when configured to increasing or to de-energize the relay when
configured to decreasing.
04 GP SW1 - LOW SET:
[*45.0 (0.0,100.0)] This is the low set point for the gate position switch. When
the switch is increasing, this set point is the reset point of the gate position switch. When the switch is
decreasing, this set point is the trip point of the gate position switch.