Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
42
11 AN IN #4-OFFSET:
[*0 (-100,100)] This menu item is the number added to the raw current throughout
the current range. This is used to adjust the current’s y-axis intercept for proper calibration.
12 AN IN #4-GAIN:
[*1 (0.5, 2)] This menu item is the number that is multiplied by the raw current
throughout the range. This is used to adjust the slope of the linear current for proper calibration.
13 AN IN #5:
[MONITOR] This menu item monitors the current on analog input #5.
14 AN IN #5-OFFSET:
[*0 (-100,100)] This menu item is the number added to the raw current throughout
the current range. This is used to adjust the current’s y-axis intercept for proper calibration.
15 AN IN #5-GAIN:
[*1 (0.5, 2)] This menu item is the number that is multiplied by the raw current
throughout the range. This is used to adjust the slope of the linear current for proper calibration.
16 AN IN #6:
[MONITOR] This menu item monitors the current on analog input #6.
17 AN IN #6-OFFSET:
[*0 (-100,100)] This menu item is the number added to the raw current throughout
the current range. This is used to adjust the current’s y-axis intercept for proper calibration.
18 AN IN #6-GAIN:
[*1 (0.5, 2)] This menu item is the number that is multiplied by the raw current
throughout the range. This is used to adjust the slope of the linear current for proper calibration.
19 AN IN #7:
[MONITOR] This menu item monitors the current on analog input #7.
20 AN IN #7-OFFSET:
[*0 (-100,100)] This menu item is the number added to the raw current throughout
the current range. This is used to adjust the current’s y-axis intercept for proper calibration.
21 AN IN #7-GAIN:
[*1 (0.5, 2)] This menu item is the number that is multiplied by the raw current
throughout the range. This is used to adjust the slope of the linear current for proper calibration.
22 AN IN #8:
[MONITOR] This menu item monitors the current on analog input #8.
23 AN IN #8-OFFSET:
[*0 (-100,100)] This menu item is the number added to the raw current throughout
the current range. This is used to adjust the current’s y-axis intercept for proper calibration.
24 AN IN #8-GAIN:
[*1 (0.5, 2)] This menu item is the number that is multiplied by the raw current
throughout the range. This is used to adjust the slope of the linear current for proper calibration.
04 CAL ANALOG OUTPUTS
This menu allows you to force the analog output to any value.
The Calibrate Mode should only be entered when the unit is shut
down, de-watered, and it is safe to move the gates. All I/O points will
be under complete manual control!
01 CALIBRATE ENABLED:
[MONITOR]
This item displays if the calibrate mode is enabled.
02 FORCED AN OUT #1:
[MONITOR] This menu item displays the value (in percent of full scale range)
that the analog output are being forced to. For example, if this menu item is displaying 25, then analog
output will be 8 mA (25% of 16 mA plus 4 mA).
03 SELECT ANALOG OUT #1:
[*1 (1,6)] This menu item selects the output current %. The integer can
be set to any of the following:
4
–20 mA
1 = 0% 4 mA
2 = 25% 8 mA
3 = 50% 12 mA
4 = 75% 16 mA
5 = 100% 20 mA
6 = Manually controlled analog value
04 MANUAL AO#1 VALUE:
[*0 (-10,110)] This menu item can be adjusted to any value between -10%
and 110% of full
scale. If the previous menu item, “SELECT ANALOG OUT,” is tuned to 6, then this
number is used to control the analog output.
05 FORCED ACTUATOR:
[MONITOR] This menu item displays the value (in percent of full scale range)
that the analog output are being forced to. For example, if this menu item is displaying 25, then analog
output will be 8 mA (25% of 16 mA plus 4 mA), if the actuator is configured to 4
–20 mA.
06 SELECT ACTUATOR OUT:
[*1 (1,6)] This menu item selects the output current %. The integer can be
set to any of the following:
4
–20 mA 0–20 mA
0
–200 mA
1 = 0% 4 mA
0 mA
0 mA
2 = 25% 8 mA
5 mA
50 mA
3 = 50% 12 mA
10 mA
100 mA