Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
63
Modbus
ID
Item Function
Semantics
1:0069
Maintenance Mode Enabled
0=False, 1=True
1:0070
Manual Mode Enabled
0=False, 1=True
1:0071
DSLC Mode Enabled
0=False, 1=True
1:0072
Auto-Follow Mode Enabled
0=False, 1=True
1:0073
Remote Reference Mode Enabled
0=False, 1=True
1:0074
Level Rem Ref Mode Enabled
0=False, 1=True
1:0075
Pond/Tail Level Control Enabled
0=False, 1=True
1:0076
Brake Permissive
0=False, 1=True
1:0077
In Control - Gate Limit
0=False, 1=True
1:0078
In Control - On-Line/Droop PID
0=False, 1=True
1:0079
In Control - Off-Line/Isoch PID
0=False, 1=True
1:0080
Speed Fault/Overspeed Override
0=False, 1=True
1:0081
Gate Limit - At 0%
0=False, 1=True
1:0082
Gate Limit - At 100%
0=False, 1=True
1:0083
Gate Limit - At Breakaway
0=False, 1=True
1:0084
Gate Limit - At Speed-No-Load/Off-Line
0=False, 1=True
1:0085
Gate Limit - At Max Gate Pos/On-Line
0=False, 1=True
1:0086
Gate Limit - Actual gate Position
0=False, 1=True
1:0087
Gate Limit - Use Analog Input
0=False, 1=True
1:0088
Remote Ref (Modbus)
0=False, 1=True
1:0089
Remote Ref (Analog)
0=False, 1=True
1:0090
PID On Line Selected
0=False, 1=True
1:0091
Turbine Stopped (speed less than 2%)
0=False, 1=True
1:0092
Off-Ln/Isoch Spd Ref - At Lower Limit
0=False, 1=True
1:0093
Off-Ln/Isoch Spd Ref - Follow Actl Pos
0=False, 1=True
1:0094
Off-Ln/Isoch Spd Ref - At Start Up
0=False, 1=True
1:0095
Off-Ln/Isoch Spd Ref - At SNL Setpoint
0=False, 1=True
1:0096
Off-Ln/Isoch Spd Ref - At Upper Limit
0=False, 1=True
1:0097
On-Ln/Droop Spd Ref - Follow Actl Pos
0=False, 1=True
1:0098
On-Ln/Droop Spd Ref - At Rem Stpnt
0=False, 1=True
1:0099
On-Ln/Droop Spd Ref - At Lvl Stpnt
0=False, 1=True
1:0100
On-Ln/Droop Spd Ref - At Lower Lim
0=False, 1=True
1:0101
On-Ln/Droop Spd Ref - At Upper Lim
0=False, 1=True
1:0102
Speed Switch #1
0=False, 1=True
1:0103
Speed Switch #2
0=False, 1=True
1:0104
Gate Position Switch #1
0=False, 1=True
1:0105
Gate Position Switch #2
0=False, 1=True
1:0106
KW Switch #1
0=False, 1=True
1:0107
KW Switch #2
0=False, 1=True
1:0108
Speed Switch #3
0=False, 1=True
1:0109
Enable Overspeed - Permissive #1
0=False, 1=True
1:0110
Enable Overspeed - Permissive #2
0=False, 1=True
Released