Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
74
SERVICE
MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MINIMUM
MAXIMUM
17 REMOTE CONTROL
01 Rem Spd Enabled
Monitor
02 Rem Spd Anlg In Enabled
Monitor
03 Rmt Spd Analog In
Monitor
04 Rem Spd Modbus Enabled
Monitor
05 Remote Spd Reference
Monitor
06 AI Value @ 4 mA
0
-200
200
07 AI Value @ 20 mA
100
-200
200
08 Remote Speed Ramp Rate
0.2
0
100
18 LEVEL CONTROL
01 Lvl Cntrl Enabled
Monitor
02 Pond/Tail Level
Monitor
03 Level Setpoint
Monitor
04 Preset Value
0
0
100000
05 Max Gate Position
100
0
100
06 Min Gate Position
20
0
100
07 Control Window
0.5
0
10000
08 Gate Position Set
Monitor
09 Signal Filter TC
2
0.01
7200
10 Raise/Lower Rate
1
0.01
1000
11 Level Gate Rate
0.05
0.001
100
19 REMOTE LEVEL CTRL
01 Rem Level Enabled
Monitor
02 Rem Lvl Anlg In Enabled
Monitor
03 Rmt Lvl Analog In
Monitor
04 Rem Lvl Modbus Enabled
Monitor
05 Remote Level Reference
Monitor
06 AI Value @ 4 mA
4
-30000
30000
07 AI Value @ 20 mA
20
-30000
30000
20 GAINS
01 Droop
5
0
10
02 Offline P Gain
1
0.001
50
03 Offline I Gain
0.2
0.001
50
04 Offline D Gain
100
0.001
50
05 Online P Gain
1
0.001
50
06 Online I Gain
0.2
0.001
50
07 Online D Gain
100
0.001
50
08 Disable Feed Fwd?
FALSE
FALSE
TRUE
09 Feed Forward Gain
1
0
1
10 Temporary Comp
0.05
0
10
11 Error Gain
1
1
100
21 GATE TIMER
01 Trn on Gate Timer
FALSE
FALSE
TRUE
02 Gate Time (sec)
Monitor
03 Reset Gate Time
FALSE
FALSE
TRUE
04 GoTo 5% Gate Pos
FALSE
FALSE
TRUE
05 GoTo 95% Gate Pos
FALSE
FALSE
TRUE
22 STEP TEST
01 Enable Step Test
FALSE
FALSE
TRUE
02 Step Duration
30
0
1200
Released