Manual – overview of system
Groupfunction
The parameters for the groupfunction has to be set as follows::
–
F23 = 3 (on each control, which is in a group)
–
F181 = 0-7 (Number of elevator in one group-the lowest number has highest priority
)
Security loop – Return-motion -control
First ashure that security loop is closed
If it is necessary to bypass parts of securityloop, precautionary measures has to be taken for
running the cabin.
One has to make shure that nobody is in the range of the doors or in the shaft!
At first connect all existant security switches and elements
If this is not possible the relevant strapping plugs should be placed.
First movement with the Return-motion -control
When it is checked that there is no danger of collision first run with return-motion-control could be
made.
If the elevator does not move in the intended direction, the correct rotation direction should only be
set via the inverter.
Please go to following menu part
F - XXX
Parameter F234 = 0 (change to 1)
Parameter F234 = 1 (change to 0)
Setting the parameters on AS.T030
Depiction 7-Segment Display on a AS.T030 board in normal operatin state