1.15.2 MIB (Manual Interface Board) Troubleshooting
Problem
Probable Causes
Corrective Action
Auto filtration won’t
start.
A.
Filter pan out of position.
B.
Oil level too low.
C.
Ensure MIB board is not in
manual mode.
D.
Ensure MIB cover is not
damaged and pressing against
buttons.
E.
Filter relay has failed.
F.
Filter motor thermal switch is
tripped.
A.
Ensure filter pan is fully inserted into fryer.
If the MIB board displays a “
P
” the pan is
not fully engaged into the pan switch.
B.
Ensure the oil level is above the top oil
level sensor.
C.
Ensure MIB board is in “
A
” automatic
mode.
D.
Remove and replace cover and see if
filtration will start.
E.
Replace filter relay with part number 807-
4482 24VDC relay.
F.
Press filter motor thermal switch.
MIB display shows
something other than
an “
A
” or vat number.
An error has occurred and
displayed character indicates
error.
See MIB display characters on page 1-34 for
explanation.
No power present at
the MIB board
Transformer has failed in left
component box.
Check output on the left transformer in left
component box; should read 24VAC. If not
replace transformer.
MIB will not clear
error.
Error remains in non-volatile
memory.
Press and hold reset button in top right corner
of MIB board for five seconds. The drain,
return and manual/auto LEDS will illuminate
and the MIB will reset and clear any remaining
errors from memory. Allow 60 seconds to reset.
If an error still exists, then another issue exists.
MIB indicates
incorrect number of
vats.
A.
Network is not terminated
correctly.
B.
Wiring harnesses are loose or
damaged.
C.
An AIF board issue.
D.
Locator pin issue.
A.
Ensure the CAN bus system is terminated at
BOTH
ENDS
(on the FilterQuick™
controller connector J6 and on the ATO
board connector J9) with a resistor equipped
6-pin connector.
B.
Unplug and reseat all wiring harnesses in
CAN system. Resistance between pins 2
and 3 on the CAN network connectors
should be 120 ohms.
C.
Check software version numbers on all
FilterQuick™ controllers and ensure all
display an AIF version. If an AIF version is
missing, the AIF board may be missing
power or bad. Check pins 5 and on J4 and
J5 of the affected AIF board for proper
voltage.
D.
The locator pin in J2 of the AIF board is
either loose or in the incorrect position. See
the charts on page 1-41 of this manual for
proper pin position.
Содержание Frymaster FilterQuick 2FQG30U
Страница 8: ...1 3 ...
Страница 41: ...1 36 1 16 2 Bulk Wiring ...
Страница 56: ...1 51 1 18 6 Clogged Drain Failed Oil Sensor Error Flowchart ...
Страница 57: ...1 52 1 18 7 Menu Trees 1 18 7 1 FilterQuick Controller Setup Menu Tree ...
Страница 58: ...1 53 1 18 7 2 FilterQuick Filter and Info Mode Menu Tree ...
Страница 62: ...1 57 1 20 Principal Wiring Connections ...
Страница 63: ...1 58 1 21 Wiring Diagrams 1 21 1 Main FQG 230 430 120V CE Export ...
Страница 64: ...1 59 1 21 2 Main FQG 230 430 Australia ...
Страница 65: ...1 60 1 21 3 Main FQG 230 430 120V CE Export with Solid Shortening ...
Страница 66: ...1 61 1 21 4 Main FQG 230 430 Australia with Solid Shortening ...
Страница 67: ...1 62 1 21 5 Main FQG 330 530 120V CE Export ...
Страница 68: ...1 63 1 21 6 Main FQG 330 530 Australia ...
Страница 69: ...1 64 1 21 7 Main FQG 330 530 120V CE Export with Solid Shortening ...
Страница 70: ...1 65 1 21 8 Main FQG 330 530 Australia with Solid Shortening ...
Страница 71: ...1 66 1 21 9 Transformer Filter Box 430 530 ...
Страница 72: ...1 67 1 22 Simplified Wiring Diagrams 1 22 1 FilterQuick FQG30 Series Simplified Wiring with Push Pull Handles ...
Страница 73: ...1 68 1 22 2 FilterQuick FQG30 Series Simplified Wiring with Push Buttons ...
Страница 74: ...1 69 1 22 3 FilterQuick FQG30 Series Data Network Flowchart ...
Страница 76: ...1 71 1 24 Shortening Melting Unit Wiring Diagram ...
Страница 77: ...1 72 1 25 Modular Basket Lift Wiring Diagram 100 120V 1 2 4 3 5 6 12 7 8050518E ...
Страница 79: ...1 74 1 27 Basket Lift Interface Harness ...