Connecting the SAI Distributor
Technical data
Supply voltage
24 V DC
Limit values
18 V DC to 30 V DC
Contact load
per pin 3 A
Reverse polarity protection
yes
Current input
module approx. 50 mA
Digital outputs
8 channels
Plug-in stations
O1, O2, O3 and O4
Grouping
two groups for every four channels with a common earth
Driver type
Highside
Current per channel
2 A
Residual current
module 8 A
Output voltage Low
0 V
Switching capacity, resistive load
max. 100 Hz
Switching capacity, inductive load
max. 1 Hz
Switching capacity, lamp load:
max. 8 Hz
Short-circuit proof
yes, switch-off in case of short-circuit and error message
Short-circuit current
at 25 °C 5.6 A
Separation of potentials to the module
electronics
none
Display elements
one yellow/red error/status LED per channel
General technical data:
Ambient temperature during operation
0 to +60 °C acc. to EN 61131-2
Ambient temperature during storage
-25 to +85 °C acc. to EN 61131-2
Protection class
IP65 / IP67
Dimensions L x W x H
175 x 30 x 32 mm
Weight 175
g
Article order number
1938680000
Article designation
SAI-AU M12 SB 8DO 2A
Table 50
Technical data for the SAI-AU M12 SB 8DO 2A
5663600000/1.4/09.09
71
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......