Project Planning with the Universal Pro
18
5663600000/1.4/09.09
Voltage drop / max. expansion
The maximum expansion of the sub-bus system de-
pends on four factors:
•
The number of stations
•
The distance between stations
•
The current load of each participant and there in-
puts
•
The resistance of the wires in use
The following formula results:
Voltage drop of the line =
current consumption of module x (line resistance x
line length x 2)
Total voltage drop =
voltage drop of line 1 + voltage drop of line 2 + volt-
age drop of line x
Voltage on last module =
Supply voltage to gateway I/O - 0.9V - total voltage
drop
Result:
When voltage to last module is greater then 18V DC
= Okay
When voltage to last module is less than 18V DC =
Not okay
We have made available a software tool to help you
calculate the residual current and voltage drop. It
can be downloaded from the Weidmueller home-
page at www.weidmueller.com.
3.3
An example - calculation of
power supply
A sub-bus system should be set up for 45 sensors
and 14 actuators. The extension distance is 30 m.
The following modules have been selected:
1 x 1938550000 Gateway IO Module 16DI M12
6 x 1938610000 Extension IO Module 8DI M12
2 x 1938640000 Extension IO Module 8DI/DO M12
1 x 1938680000 Extension I/O Module 8DO M12 2A
All sensors consume 10 mA current each.
No.
Cat. No.
Current for module
Current for sensors
Total current
1
1938610000
50 mA
6 x 10 mA = 60 mA
110 mA
2
1938680000
50 mA
50 mA
3
1938610000
50 mA
6 x 10 mA = 60 mA
110 mA
4
1938610000
50 mA
6 x 10 mA = 60 mA
110 mA
5
1938640000
50 mA
4 x 10 mA = 40 mA
90 mA
6
1938610000
50 mA
6 x 10 mA = 60 mA
110 mA
7
1938640000
50 mA
4 x 10 mA = 40 mA
90 mA
8
1938610000
50 mA
6 x 10 mA = 60 mA
110 mA
9
1938610000
50 mA
6 x 10 mA = 60 mA
110 mA
Table 3
Current consumption of the modules
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......