Commissioning the PROFIBUS-DP
110
5663600000/1.4/09.09
6.6.7
SAI-AU M12 SB 4PT100
Data
Describtion
input
4PT100
4 PT100 inputs
4 16bit wide words
temeratures:
16 bit two complement value :
1 Bit (digit) = 1/10 Kelvin
resistor
values:
range up to 500 Ohm :
1 Bit (digit) = 0,01 Ohm
range up to 5k Ohm
1 Bit (digit) = 0,1 Ohm
output None
NOTE
It is possible to use the status data of the PT100 module as input data. Then the user must
chose the module named “
"4PT100 M12 (input+status)".
Then the input data are formed
of the two counters and the status data (as seen in the Chapter diagnostic data).
6.6.8
SAI-AU M12 SB 4THERMO
Data
Describtion
input
4THERMO
4 THERMO inputs
4 16bit wide words
temeratures:
16 bit two complement value :
1 Bit (digit) = 1/10 Kelvin
voltages :
-250 to 250 mV :
1 Bit (digit) = 8µV
-120 to 120 mV :
1 Bit (digit) = 4µV
-60 to 60 mV :
1 Bit (digit) = 2µV
-30 to 30 mV :
1 Bit (digit) = 1µV
-15 to 15 mV :
1 Bit (digit) = 0,5µV
range up to 5k Ohm
1 Bit (digit) = 0,1 Ohm
output None
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......