Connecting the SAI Distributor
78
5663600000/1.4/09.09
Module connection from SUB-OUT
Contact system
M8 female connector, 4-pole
Coding -
Pin assignment
Pin 1: + 24 Vdc
Pin 2: Data +
Pin 3: GND
Pin 4: Data -
Housing: Shield, connected
with the FE
Table 58
Contact assignment for the sub-bus
female connector
Connection for an analogue output
Contact system
M12 female connector, 5-pole
Coding A
Pin assignment
Pin 1: + 24 Vdc actuator
voltage / 140 mA / max.
at 20°C
Pin 2: Analogue output voltage
Pin 3: GND
Pin 4: Analogue output current
Pin 5: PE
Housing: Shield
Table 59
Contact assignment for the analogue
output
Figure 49
Temperature curve
Block diagram of an analogue output
Output wiring of pins 4 and 2 for each M12 female
connector:
Figure 50
Block diagram of the analogue output
NOTE
A four-pole M8 male connector and a
four-pole M8 female connector are used
to connect the supply voltage to the sub-
bus. Use the SUB-IN connection to feed
in the power supply and the SUB-OUT
connection to forward the power further.
The power supply and the analogue
outputs share a common earth and are
not electrically isolated.
The choice of the output signal (current or voltage) is
made by selecting the pins. The current or voltage
range is selected in the configurator of the manufac-
turer of the controls.
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......