Connecting the SAI Distributor
80
5663600000/1.4/09.09
Technical data
Supply voltage
24 V DC
Limit values
18 V DC to 30 V DC
Contact load
per pin 3 A
Reverse polarity protection
yes
Current input
module approx. 50 mA
Analogue outputs
4 channels
Plug-in stations
AO0, AO1, AO2 and AO3
Output interval
5-250 ms adjustable per analogue output
Accuracy
< 0.2 % from the upper limit of effective range
Offset error
< 0.1 % from the upper limit of effective range
Linearity
< 0.05 %
Temperature coefficient
< 300 ppm/K of upper limit of effective range
Voltage ranges
0 to +10 V or –10 V to +10 V
Load resistance
1 k
Ω
Resolution from 0 V to +10 V
11-bit, 0 to 2047 units
Resolution from -10 V to +10 V
12-bit, 0 to 4095 units
Output
asymmetric (pin 2)
Current ranges
0 to 20 mA or 4 to 20 mA
Load resistance
< 600
Ω
Resolution 0 to 20 mA
11-bit, 0 to 2047 units
Resolution 4 to 20 mA
12-bit, 819 to 4095 units
Output
asymmetric (pin 4)
General technical data:
Ambient temperature during operation
0 to +60 °C acc. to EN 61131-2
Ambient temperature during storage
-25 to +85 °C acc. to EN 61131-2
Protection class
IP65 / IP67
Dimensions L x W x H
155 x 30 x 32 mm
Weight 150
g
Article order number
1938700000
Article designation
SAI-AU M12 SB 4AO
Table 60
Technical data, SAI-AU M12 SB 4AO
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......