Commissioning the PROFIBUS-DP
126
5663600000/1.4/09.09
SAI SB 4AO
Byte 1
Short circuit to +24V DC sensor supply
Byte 2
Range error indication
Bit 0 : Channel 1 value underrun
Bit 1 : Channel 2 value underrun
Bit 2 : Channel 3 value underrun
Bit 3 : Channel 4 value underrun
Table 86
Device-related diagnostic data IO of modules 4AO
SAI SB PT100
Byte 1
Range error indication
Bit 0 : Channel 1 range error
Bit 1 : Channel 2 range error
Bit 2 : Channel 3 range error
Bit 3 : Channel 4 range error
Byte 2
Broken wire status
Bit 0 : Channel 1 broken wire
Bit 1 : Channel 2 broken wire
Bit 2 : Channel 3 broken wire
Bit 3 : Channel 4 broken wire
Byte 3
Alarm threshold status
Bit 0 : Channel 1 Threshold alarm 1 active
Bit 1 : Channel 2 Threshold alarm 1 active
Bit 2 : Channel 3 Threshold alarm 1 active
Bit 3 : Channel 4 Threshold alarm 1 active
Bit 4 : Channel 1 Threshold alarm 2 active
Bit 5 : Channel 2 Threshold alarm 2 active
Bit 6 : Channel 3 Threshold alarm 2 active
Bit 7 : Channel 4 Threshold alarm 2 active
Table 87
Device-related diagnostic data IO of modules 4PT100
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......