Connecting the SAI Distributor
5663600000/1.4/09.09
89
5.14 SAI-AU M12 SB 2CNT
The SAI distributor Active Universal is equipped with
the functions of a decentralised I/O system. Each
distributor is equipped with module-specific actua-
tor/sensor functions and a sub-bus interface. The
modules combine the complete electronics in a wa-
ter- and dust-proof protected housing. This enables
their use in harsh environments. The module SAU-
AU M12 SB 2CNT is designed to connect two digital
signals for counting purpose with four M12 connec-
tors.
Figure 58
SAI-AU M12 SB 2CNT
HINWEIS
After a fallout, mistake or restart, the
ouptput bytes must be reset over the
software. The counter clearance of the
gateways is to be made with the corre-
sponding bits in the counter channel
(chapter 6.6.9). If the output data be
changed, the bit 7 in the counter chan-
nel needs to be changed from 1 into 0.
LEDs
UB
Supply voltage UB
Supplies the module and the
Plug-in stations 1 to 4
Com
Communication with the gate-
way
CN
Status of counter channels
V/R
Direction of counter channels
GT
Gate status of channels
OUT
Status of digital outputs
Connections
SUB IN
Sub-bus input
SUB OUT
Sub-bus output
AUX
Auxiliary supply for digital out-
puts
1
2 digital outputs of both channels
2
Gate input for both channels
3
Direction input for both channels
4
Counter input for both channels
Table 71
SAI-AU M12 SB 2CNT
Connection of supply voltage
The power supply is 24 V DC in accordance with
EN 61131-2; the permissible range is 18 to 30 V DC.
The dis-tributor is designed to offer protection
against polarity reversal.
OUT
GT
V/R
CN
CNT
U
B
COM
UQ1
IN
OUT
BUS
AUX
IN
Weidmüller t
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......