Connecting the SAI Distributor
Technical data
Supply voltage
24 V DC
Limit values
18 V DC to 30 V DC
Contact load
per pin 3 A
Reverse polarity protection
yes
Current input
module approx. 50 mA
Analogue inputs
4 channels
Plug-in stations
AI0, AI1, AI2 and AI3
Grouping
One group for all four channels with a common earth
Permissible input voltage
-30 V DC to +30 V DC (protected against polarity reversal)
Input Type
Differential measurement between pin 2 and pin 4
Sampling period
5 -250 ms adjustable per analogue input
Accuracy
< 0.2 % from the upper limit of effective range
Offset error
< 0.1 % from the upper limit of effective range
Linearity
< 0.05 %
Temperature coefficient
< 300 ppm/K of upper limit of effective range
Voltage ranges
0 to +10 V or –10 V to +10 V
Max. input voltage based on GND
± 35 V based on GND (continuous)
Input resistance
> 100 k
Ω
Resolution from 0 V to +10 V
11-bit, 0 to 2047 units
Resolution from -10 V to +10 V
12-bit, 0 to 4095 units
Nominal value
2047 units and 4095 units respectively
Current ranges
0 to 20 mA or 4 to 20 mA
Max. input current, differential
-50 to +50 mA
Input resistance
< 125
Ω
Resolution 0 to 20 mA
12-bit, 0 to 4095 units
Resolution 4 to 20 mA
12-bit, 819 to 4095 units, with evaluation of diagnosis
when current falls below 4 mA
Nominal value
4095 units
5663600000/1.4/09.09
75
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......