Connecting the SAI Distributor
88
5663600000/1.4/09.09
Technical data
Supply voltage
24 V DC
Limit values
18 V DC to 30 V DC
Contact load
per pin 3 A
Reverse polarity protection
yes
Current input
module approx. 50 mA
Analogue inputs
4 channels
Plug-in stations
AI0, AI1, AI2 and AI3
Grouping
One group for four channels
Permissable common-mode voltage
+/- 50V
Permissible input voltage
-3 V DC to +3 V DC
Input Type
PT100, PT200, PT500, PT1000, NI100, NI120, NI1000,
500
Ω
, 5k
Ω
, Potentiometer 100-500
Ω
, Poti 500-5k
Ω
,
Poti
>
5k
Ω
, No Sensor
Sampling period
54-620 ms adjustable per analogue input
Accuracy
< 0.5 % from the upper limit of effective range
Temperature coefficient
< 300 ppm/K of upper limit of effective range
Sensor current
depending on input type, 0.2mA or 0.5mA
Resolution of temperature sensors
0.1 °C
Resolution of resistant measurement
range
500
Ω
: 0.01
Ω
5k
Ω
: 0.1
Ω
General technical data:
Ambient temperature during operation
0 to +60 °C acc. to EN 61131-2
Ambient temperature during storage
-25 to +85 °C acc. to EN 61131-2
Protection class
IP65 / IP67
Dimensions L x W x H
155 x 30 x 32 mm
Weight 150
g
Article order number
1938710000
Article designation
SAI-AU M12 SB 4PT100
Table 70
Technical data, SAI-AU M12 SB 4PT100
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......