Connecting the SAI Distributor
5663600000/1.4/09.09
NOTE
A five-pole M12 male connector is used
to connect the supply voltage to the sub-
bus. Use the SUB-OUT connection as a
feed-through. The power supply and the
digital inputs share a common earth and
are not electrically isolated.
Connection of supply voltage
The power supply is 24 V DC in accordance with EN
61131-2; the permissible range is 18 to 30 V DC.
The distributor is designed to offer protection against
polarity reversal.
Module connection from AUX-IN
Contact system
M12 male connector, 5-pole
Coding A
Pin assignment
Pin 1: + 24 Vdc UI1
Pin 2: + 24 Vdc UI2
Pin 3: GND
Pin 4: GND
Pin 5: PE
Module connection from SUB-OUT
Contact system
M8 female connector, 4-pole
Coding A
Pin assignment
Pin 1: +24 Vdc
Pin 2: Data +
Pin 3: GND
Pin 4: Data -
Housing: Shield, connected with
the FE
Table 13
Contact assignment for the AUX-IN
male connector
Table 14
Contact assignment for the Sub-bus
female connector
Block diagram of the digital input
Connection for a digital input
Contact system
M8 female connector, 3-pole
Coding None
Pin assignment
Pin 1: + 24 Vdc sensor power
supply
Pin 2: GND
Pin 4: Input
Input configuration pins 2 and 4 from each M12 fe-
male connector:
Table 15
Contact assignment of the digital input
Figure 19
Block diagram of the digital input
39
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......