Commissioning the PROFIBUS-DP
6.6.5
SAI-AU M12 SB 4AI
Data
Describtion
input
4AI
4 analog inputs
4 16 bit wide words (only lower 11 or 12 bits are used)
depending on range these values will occur:
0..10 V
:
0.. 2047
-10..+10 V
0 .. 4095 (where 2047 equals 0 V)
0..20 mA
:
0 .. 4095
4..20
mA : 819
output None
6.6.6
SAI-AU M12 SB 4AO
Data
Describtion
input None
output
4AO
4 analog outputs
4 16bit wide words (only lower 11 or 12 bits are used)
depending on range these values must be written:
0..10 V
:
0.. 2047
-10..10 V
0 .. 4095 (where 2047 equals 0 V)
0..20 mA
:
0 .. 4095
4..20 mA
:
819 .. 4095
5663600000/1.4/09.09
109