Commissioning the PROFIBUS-DP
128
5663600000/1.4/09.09
6.9.2
Diagnostics with channel referred information
Parameter: „Extended Diagnostic“ Enable
This diagnosis consists of four parts:
1. Six bytes of standard diagnostics
2. 35 bytes Device-related diagnosis
3. 2-3 bytes of identification-referred diagnosis (Number depends on number of attached Extension IO mod-
ules <= 7 = 2 bytes, >7 = 3 bytes)
4. n bytes channel-referred diagnosis (The channel-referred diagnosis is as largely as the number of arising
errors times three bytes)
Standard diagnostics
Byte 0, station status 1
Bit 0
station_non_exist
1 = station can not be reached; always "0"
Bit 1
station_not_ready
1 = station is not ready for data exchange
Bit 2
cfg_fault
1 = configuration error with the master
Bit 3
ext_diag
1 = extended diagnostics data is available
Bit 4
not_supported
1 = a requested function is not supported
Bit 5
invalid_slave_response
1 = the slave response was not valid
Bit 6
prm_fault
1 = false or incomplete parameter data
Bit 7
master_lock
1 = parameters are from another master set - access is locked
Byte 1, station status 2
Bit 0
Prm_req
1 = parameter must be transmitted again
Bit 1
Stat_diag
1 = diagnostic data is present
Bit 2
“1”
Slave always sets "1"
Bit 3
WD_ON
1 = The slave has activated the watchdog
Bit 4
freeze_mode
1 = The slave has received the "freeze" control command
Bit 5
sync_mode
1 = The slave has received the "sync" control command
Bit 6
reserved
Slave always sets "0"
Bit 7
deactivated
1 = set from master, slave is inactive, slave always sets "0"
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......