Troubleshooting and Maintenance
CFW-11W G2 | 6-7
6
Fault/Alarm
Description
Possible Causes
A327:
High Temperature IGBT U B4
Alarm of high temperature measured on the
temperature sensor (NTC) of IGBT of phase U
of book 4. Measured temperature above 110 ºC
(230 °F).
High coolant temperature (> 45 °C (113 °F) see
Item 3.1.6 Cooling System on page 3-9
) and
high output current.
Coolant flow < 20l/min or clogged tubing.
UP11W heatsink or system heat exchanger rust
inside due to coolant out of the specifications (see
Item 3.1.3 Lifting on page 3-2
Fault in the pumps.
F328:
Overtemperature
IGBT U B4
Fault of overtemperature measured on the
temperature sensor (NTC) of the IGBT of phase U
of book 4. Measured temperature above 115 ºC
(239 °F).
A330:
High Temperature
IGBT V B4
Alarm of high temperature measured on the
temperature sensor (NTC) of IGBT of phase V
of book 4. Measured temperature above 110 ºC
(230 °F).
F331:
Overtemperature
IGBT V B4
Fault of overtemperature measured on the
temperature sensor (NTC) of IGBT of phase V
of book 4. Measured temperature above 115 ºC
(239 °F).
A333:
High Temperature
IGBT W B4
Alarm of high temperature measured on the
temperature sensor (NTC) of IGBT of phase W
of book 4. Measured temperature above 110 ºC
(230 °F).
F334:
Overtemperature
IGBT W B4
Fault of overtemperature measured on the
temperature sensor (NTC) of IGBT of phase W
of book 4. Measured temperature above 115 ºC
(239 °F).
A336:
High Temperature
IGBT U B5
Alarm of high temperature measured on the
temperature sensor (NTC) of IGBT of phase U
of book 5. Measured temperature above 110 ºC
(230 °F).
F337:
Overtemperature
IGBT U B5
Fault of overtemperature measured on the
temperature sensor (NTC) of the IGBT of phase U
of book 5. Measured temperature above 115 ºC
(239 °F).
A339:
High Temperature
IGBT V B5
Alarm of high temperature measured on the
temperature sensor (NTC) of IGBT of phase V
of book 5. Measured temperature above 110 ºC
(230 °F).
F340:
Overtemperature
IGBT V B5
Fault of overtemperature measured on the
temperature sensor (NTC) of IGBT of phase V
of book 5. Measured temperature above 115 ºC
(239 °F).
A342:
High Temperature
IGBT W B5
Alarm of high temperature measured on the
temperature sensor (NTC) of IGBT of phase W
of book 5. Measured temperature above 110 ºC
(230 °F).
F343:
Overtemperature IGBT
W B5
Fault of overtemperature measured on the
temperature sensor (NTC) of IGBT of phase W
of book 5. Measured temperature above 115 ºC
(239 °F).
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...