Installation and Connection
CFW-11W G2 | 3-35
3
CCW
CW
≥5 kΩ
rpm
amp
XC1
Terminal
Strip
Factory Default Function
Specifications
1
REF+
Positive reference for
potentiometer
Output voltage: +5.4 V, ±5 %
Maximum output current: 2 mA
2
AI1+
Analog input #1:
speed reference (remote)
Differential
Resolution: 12 bits
Signal: 0 to 10 V (RIN = 400 kΩ) / 0 to 20 mA / 4 to 20 mA (RIN = 500 Ω)
Maximum voltage: ±30 V
3
AI1-
4
REF-
Negative reference for
potentiometer
Output voltage: -4.7 V, ±5 %
Maximum output current: 2 mA
5
AI2+
Analog input #2:
no function
Differential
Resolution: 11 bits + signal
Signal: 0 to ±10 V (RIN = 400 kΩ) / 0 to 20 mA / 4 to 20 mA (RIN = 500 Ω)
Maximum voltage: ±30 V
6
AI2-
7
AO1
Analog output #1:
Speed
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (RL ≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (RL ≤ 500 Ω)
Protected against short-circuit
8
AGND
(24 V)
Reference (0 V) for the
analog outputs
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor
9
AO2
Analog output #2:
Motor current
Galvanic isolation
Resolution: 11 bits
Signal: 0 to 10 V (RL ≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (RL ≤ 500 Ω)
Protected against short-circuit
10
AGND
(24 V)
Reference (0 V) for the
analog outputs
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor
11 DGND*
Reference (0 V) for the
24 Vdc power supply
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor
12
COM
Common point of the digital
inputs
13 24 Vcc
24 Vdc power supply
24 Vdc power supply, ±8 %
Capacity: 500 mA
Note:
in the models with the 24 Vdc external control power supply
(CFW11XXXXXOW) the terminal 13 of XC1 becomes an input, i.e., the user
must connect a 24 Vdc power supply for the inverter (refer to the
Safety Stop Function on page 7-2
, for more details). Inall the other models
this terminal is an output, i.e., the user has a 24 Vdc power supply available
there
14
COM
Common point of the digital
inputs
15
DI1
Digital input #1:
Start / Stop
6 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Input voltage ≤ 30 V
Input current: 11 mA @ 24 Vdc
16
DI2
Digital input #2:
direction of rotation (remote)
17
DI3
Digital input #3:
no function
18
DI4
Digital input #4:
no function
19
DI5
Digital input #5:
jog (remote)
20
DI6
Digital input #6:
2nf ramp
21
NF1
Digital output #1 DO1 (RL1):
no fault
Contact rating:
Maximum voltage: 240 Vac
Maximum current: 1 A
NC - Normally closed contact
C - Common
NO - Normally open contact
22
C1
23
NA1
24
NF2
Digital output #2 DO2 (RL2):
N > NX 25 C2 - Speed >
P0288
25
C2
26
NA2
27
NF3
Digital output #3 DO3 (RL3):
N* > NX - Speed reference >
P0288
28
C3
29
NA3
Figure 3.41:
Signals of connector XC1 - Digital inputs as active low
NOTE!
In order to use the digital inputs as active low, it is necessary to remove the jumper between XC1: 11
and 12 and change it to XC1: 12 and 13.
Содержание CFW-11W G2 RB Series