Energization and Start-Up
CFW-11W G2 | 5-3
5
5.2.2 Oriented Start-up
In order to simplify the setting of the inverter, there is a parameter group called Oriented Start-Up. Within this group
is parameter P0317, which can be used to access the Oriented Start-Up.
The Oriented Start-up routine shows on the HMI the main parameters in a logical sequence, so that their setting,
according to the operating conditions, prepares the inverter for operation according to the supply voltage and
motor used.
In order to enter an Oriented Start-up routine, follow the sequence presented in
, first
changing P0317 = 1, and then setting the other parameters as they are displayed on the HMI.
The setting of the parameters presented in this operating mode automatically changes the content of other inverter
parameters and/or internal variables.
During the Oriented Start-Up routine the “Config” (Configuration) status will be indicated on the top left part of
the HMI.
Step
Action/Result
Display Indication
Step
Action/Result
Display Indication
1
- Monitoring mode
- Press
"Menu"
(right soft
key)
Ready
LOC
0rpm
13:48
Menu
0
rpm
0.0
A
0.0
Hz
11
- If needed, change the
value of P0298 according
to the inverter application.
To do so, press
"Select"
.
This modification will affect
P0156, P0157, P0158, P0401,
P0404 and P0410 (this last
one only if P0202 = 0, 1, or
2 - V/f control). The time and
the activation level of the
overload protection will be
affected as well
Config LOC
0rpm
Reset
13:48 Select
Line Rated Voltage
P0296: 500 - 525 V
Application
P0298: Heavy Duty
2
- Group
"00 ALL
PARAMETERS"
has been
already selected
Ready
LOC
0rpm
Return
13:48 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
12
- If needed, change the
value of P0398 according
to the motor service factor
To do so, press
"Select"
This modification will affect
the current value and the
activation time of the motor
overload function
Config LOC
0rpm
Reset
13:48 Select
Application
P0298: Heavy Duty
Motor Service Factor
P0398: 1.15
3
- Group
"01 PARAMETER
GROUPS"
is selected
Ready
LOC
0rpm
Return
13:48 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
13
- If needed, change the
value of P0400 according
to the motor rated voltage
To do so, press
"Select"
This modification adjusts
the output voltage by a
factor x = P0400/P0296
Config LOC
0rpm
Reset
13:48 Select
Motor Service Factor
P0398: 1.15
Motor Rated Voltage
P0400: 525 V
4
- Group
"02 ORIENTED
START-UP"
is then selected
- Press
"Select"
Ready
LOC
0rpm
Return
13:48 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
14
- If needed, change the
value of P0401 according
to the motor rated current.
To do so, press
"Select"
.
This modification will affect
P0156, P0157, P0158, and
P0410
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Voltage
P0400: 440V
Motor Rated Current
P0401: 30.2 A
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...