Troubleshooting and Maintenance
6-10 | CFW-11W G2
6
Fault/Alarm
Description
Possible Causes
A402:
Current unbalance
Phase U B5
Alarm of current imbalance of phase U book 5.
It indicates an imbalance of 20 % in the current
distribution between this phase and the smallest
current of the same phase in another book, only
when the current in this phase is higher than 75 %
of its rated value.
Poor electrical connection between the DC link
and the power unit.
Poor electrical connection between the power
unit output and the motor.
Note:
In case of quick accelerations and brakes,
this alarm may be momentarily indicated,
disappearing after some seconds. This does not
indicate a malfunction on the inverter. In case this
alarm persists when the motor is operating at
constant speed, it is an indication of abnormal
current distribution between the power units.
A403:
Current unbalance
Phase V B5
Alarm of current imbalance of phase V book 5.
It indicates an imbalance of 20 % in the current
distribution between this phase and the smallest
current of the same phase in another book, only
when the current in this phase is higher than 75 %
of its rated value.
A404:
Current unbalance
Phase W B5
Alarm of current imbalance of phase W book 5.
It indicates an imbalance of 20 % in the current
distribution between this phase and the smallest
current of the same phase in another book, only
when the current in this phase is higher than 75 %
of its rated value.
F406:
Overtemperature on the
Braking Module.
This fault/alarm is linked to the configuration of
parameters P0832 and P0833.
- Function of input DIM 1.
- Function of input DIM 2.
Fault on the cooling of the braking module.
Load inertia too high or deceleration ramp too fast.
Load on the motor shaft is too high.
F408:
Fault on the Cooling System
Pump fault.
Fault on the panel ventilation.
F410:
External Fault
Input DIM1 or DIM2 open. Check the drive used
in the application.
F412:
Overtemperature on the
Rectifier
Ambient temperature around the rectifier (>45 °C
(113 °F)) and output current too high.
Cooling problem on the rectifier.
Rectifier heatsink too dirty.
F414:
Fault on the External Rectifier
Undervoltage or phase loss in the rectifier input.
A415:
High temperature on Rectifier
High ambient temperature around the rectifier
and high output current.
Rectifier heatsink too dirty.
A700:
(5)
HMI Disconnected
Alarm or Fault linked to the disconnection of the
HMI.
RTC function block was enabled in the SoftPLC
application and the HMI is disconnected from
the inverter.
F701:
(5)
HMI Disconnected
A702:
(5)
Inverter Disabled
Alarm indicates the General Enable command is
Disabled.
Run/Stop command of the SoftPLC application
or the movement block was enabled with the
inverter in general disabled.
A704:
(5)
Two Movements Enabled
Two movements enabled.
It occurs when two or more movement blocks
are simultaneously enabled.
A706:
(5)
Reference Not Set for SoftPLC
Reference not set for SoftPLC.
It occurs when a movement block is enabled and
the speed reference is not configured for SoftPLC
(check P0221 and P0222).
Models in which it may occur:
(1)
In the case of the CFW11W G2, the HMI does not indicated in which UP11W G2 the fault occurred. LEDs on the ICUP board indicate which UP11W caused
the fault,
. When the reset is executed, the LEDs turn off and turn back on if the fault persists.
Figure 6.1:
LEDs that indicate fault on the arms of the power units (desaturation)
(2)
With Profibus DP module connected to slot 3 (XC43).
(3)
With IOE-01 (02 or 03) module connected to slot 1 (XC41).
(4)
Motor connecting cable too long, over 100-meter long, will present a high stray capacitance to the ground. The circulation of eddy currents in these
capacitances may cause the activation of the ground fault circuit and, consequently, blocking due to F074 immediately after the inverter is enabled.
(5)
All models with SoftPLC application.
NOTE!
The range from P0750 to P0799 is intended for user's Faults and Alarms of the SoftPLC application.
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...