Installation and Connection
CFW-11W G2 | 3-33
3
Figure 3.37:
ICUP shield fastened to the panel
The control rack must be grounded using a flat flexible braid with minimum width of 5 mm and minimum cross-
section of 3 mm² with standard FASTON terminal 6.35 mm (E.g.: TYCO 735075-0 and 180363-2) and lug terminal
M4; see
.
Flexible Braid
Figure 3.38:
Control rack grounding
The panel door must be grounded with flexible braid.
Figure 3.39:
Grounding of the panel door