Installation and Connection
3-18 | CFW-11W G2
3
3.2.1.6 Harmonics of the 18-Pulse Rectifier
and
show the typical harmonic
content values of the currents, Power Factor and THD(I) on the power line, considering the 18-pulse rectifier.
Table 3.11:
Typical individual harmonics, Power Factor and THD(I) for rated load in the output. 18-pulse rectifier
Harmonic
Order
I(%)
FP
THD(I)
1
100.0 %
0.97
3.2 %
5
0.2 %
7
0.0 %
11
0.1 %
13
0.0 %
17
2.5 %
19
1.9 %
23
0.0 %
Nor
ma
liz
ed
Ha
rm
on
ic
A
mpl
itud
e
Load percentage
5ª Harmonic
7ª Harmonic
11ª Harmonic
13ª Harmonic
17ª Harmonic
19ª Harmonic
23ª Harmonic
0 %
0,0 %
0,5 %
1,0 %
1,5 %
2,0 %
2,5 %
3,0 %
20 %
40 %
60 %
80 %
100 %
120 %
Note:
Amplitude of the normalized harmonics as a function of the fundamental with 100 % of load. 18-pulse rectifier
Figure 3.22:
Typical input current harmonic values with variation of the output power
0.971
0.968
0.967
0.966
0.965
0 %
6.0 %
5.5 %
5.0 %
4.0 %
3.5 %
3.0 %
20 %
40 %
60 %
80 %
100 %
120 %
0.97
0.969
P
ow
er f
ac
to
r
THD
4.5 %
Load percentage
Figure 3.23:
Power Factor (PF) and THD (I) with variation of the output power. 18-pulse rectifier
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...