Installation and Connection
CFW-11W G2 | 3-31
3
The control rack is powered via connector XC9, located on the ICUP board; it is described in
.
Table 3.18:
Description of connector XC9
XC9
Function
Specifications
1
+24 Vcc
Positive pole of the +24 Vdc power supply
24 Vdc power supply (± 3 %)
Consumption: 1.25 A
2
NC
Not connected
3
GND
Reference of the +24 Vdc power supply
DIP switches S1 and S2,
, have the function, respectively, to select the level of the
inverter alternating supply voltage and the number of UP11W G2 connected.
S2
S1
Figure 3.35:
Detail of DIP switches S1 and S2
Table 3.19:
DIP switch S1:1 - S1:3 configuration
S1:3
S1:2
S1:1
Alternate Supply
Voltage
OFF
OFF
OFF
500 - 690 V
Table 3.20:
DIP switch S1:4 configuration
S1:4
Operating Mode
OFF
Normal
ON
Reduced Power
The operating mode with reduced power is detailed in
Section 5.7 OPERATION WITH A REDUCED NUMBER OF
Table 3.21:
DIP switch S2 configuration
S2:4
S2:3
S2:2
S2:1
Number of UP11W
Connected
OFF
OFF
OFF
OFF
1
OFF
OFF
OFF
ON
2
OFF
OFF
ON
ON
3
OFF
ON
ON
ON
4
ON
ON
ON
ON
5