![WEG CFW-11W G2 RB Series Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/weg/cfw-11w-g2-rb-series/cfw-11w-g2-rb-series_user-manual_950738047.webp)
Installation and Connection
3-30 | CFW-11W G2
3
The electronics of the UP11W G2 is powered via connector XC6, located on the IUP board; it is described in
Table 3.16:
Description of connector XC6
XC6
Function
Specifications
1
+24 Vcc
Positive pole of the +24 Vdc power supply
24 Vdc power supply(± 3 %)
Consumption: 750 mA per UP11W G2
2
NC
Not connected
3
GND
Reference of the +24 Vdc power supply
3.2.12.2 UC11 G2 Connections
DIM1 and DIM2 digital inputs located on the ICUP1 board (
) can be programmed via
parameters P0832 and P0833 respectively.
Table 3.17:
Function of the signals on the connector XC5
Connector XC5
Factory Default Function
Specifications
1
DIM1
DIM1 isolated digital input, programmable in (P0832).
Refer to the programming manual
High level ≥ 18 V
Low level ≤ 3 V
Maximum input voltage: 30 V
Input current: 11 mA @ 24 Vdc
2
DIM2
DIM2 isolated digital input, programmable in (P0833).
Refer to the programming manual
3
COM
Common point of the digital inputs of the ICUP1 board
4
+24 V
24 Vdc power supply
Isolated power supply 24 Vdc ± 8 %
Capacity: 600 mA
Note 1:
This power supply can be used to power DIM1 (ISOL)
and DIM2 (ISOL) digital inputs of the ICUP1 board
Note 2:
This power supply is isolated from the 24 Vdc input
used to power ICUP1
Note 3:
This is the same power supply available on the CC11
board
5
GND_24 0 V reference for the 24 Vdc power supply
Fiber optics
connectors
(connection to UP11)
Connectors DB25
XC40A to XC40E
(connection to UP11)
XC5: DIM1 and DIM2
Digital Inputs
XC9: 24 Vdc
Power Supply
XC60: Connection
to control rack
XC67: Connection to
the control rack (safety
stop)
DIP
switches
S1 and S2
Fiber optics
connectors reserved
for WEG use
Figure 3.34:
ICUP board connection points
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...