Technical Data
8-2 | CFW-11W G2
8
Table 8.1:
Inverter technical data for rated switching frequencies
Model
CFW11W G2
0780 T 6
CFW11W G2
1482 T 6
CFW11W G2
2223 T 6
CFW11W G2
2964 T 6
CFW11W G2
3705 T 6
Power Supply [V
dc
]
574...1150
Nº of UP11
1
2
3
4
5
Normal
Duty (ND)
Rated Output Current [Arms]
780
1482
2223
2964
3705
Overload Current
[Arms]
1 min
858
1630
2445
3260
4076
3 s
1170
2223
3335
4446
5558
Switching Frequency [kHz]
2
2
2
2
2
Maximum Motor [cv/kW]
1000/750
2000/1500
3000/2250
4000/3000
5000/3750
Rated Input Current [Adc]
897
1704
2556
3409
4261
Dissipated Power
[kW]
For the Coolant
10,5
21,0
31,5
42,0
52,5
For the Air
0,2
0,4
0,6
0,8
1,0
Heavy
Duty (HD)
Rated Output Current [Arms]
640
1216
1824
2432
3040
Overload Current
[Arms]
1 min
960
1824
2736
3648
4560
3 s
1280
2432
3648
4864
6080
Switching Frequency [kHz]
2
2
2
2
2
Maximum Motor [cv/kW]
800/600
1500/1100
2200/1600
3000/2200
3800/2800
Rated Input Current [Adc]
736
1398
2098
2797
3496
Dissipated Power
[kW]
For the Coolant
8,7
17,4
26,1
34,8
43,5
For the Air
0,2
0,4
0,6
0,8
1,0
Note:
(1)
Steady state rated current in the following conditions:
- Indicated switching frequency. It is not possible to use the CFW11W G2 inverter with switching frequency of 2.5 kHz, 5 kHz and 10 kHz.
- Ambient temperature around the inverter as specified in
Chapter 3 INSTALLATION AND CONNECTION on page 3-1
. For higher temperatures, limited
to 55 º C, the output current must be derated by 0,5 % for each º C above the maximum temperature specified.
- Coolant input temperature as specified in
Chapter 3 INSTALLATION AND CONNECTION on page 3-1
. For higher temperatures, limited to 55 º C, the
output current must be derated by 1 % for each º C above the maximum temperature specified.
- Coolant flow as specified in
Chapter 3 INSTALLATION AND CONNECTION on page 3-1
- Air relative humidity: 5 % to 95 % non-condensing.
- Altitude: 1000 m. Above 1000 m up to 4000 m, the output current must be derated by 1 % for each 100 m above 1000 m.
- Environment with pollution degree 2 (as per EN50178 and UL508C).
- For operation of the inverter in steady state with output frequencies between 0 and 10 Hz, derate the rated output current by 35 %.
(2)
One overload every 10 minutes.
presents only two points of the overload curve (actuation time of 1 min and 3 s). The complete
overload curves of the IGBTs for Normal Duty (ND) and Heavy Duty (HD) are presented in
. Depending on the inverter operating
conditions, such as ambient temperature around the inverter and output frequency, the maximum operating time of the inverter with overload may be shorter.
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...