3.2.1.5 Harmonics of the 12-Pulse Rectifier
,
and
show the typical harmonic
content values of the currents, Power Factor and THD(I) on the power line, considering the 12-pulse rectifier.
Table 3.10:
Typical individual harmonics, Power Factor and THD (I) for rated load in the output. 12-pulse rectifier
Harmonic
Order
I (%)
FP
THD (I)
1
100.0 %
0.96
7.1 %
5
0.0 %
7
0.0 %
11
6.0 %
13
3.2 %
17
0.0 %
19
0.0 %
23
1.1 %
Nor
ma
liz
ed
Ha
rm
on
ic
A
mpl
itud
e
0 %
1 %
2 %
3 %
4 %
5 %
6 %
7 %
20 %
40 %
60 %
80 %
100 %
120 %
0 %
Load percentage
5ª Harmonic
7ª Harmonic
11ª Harmonic
13ª Harmonic
17ª Harmonic
19ª Harmonic
23ª Harmonic
Note:
Amplitude of the normalized harmonics as a function of the fundamental with 100 % of load. 12-pulse rectifier.
Figure 3.20:
Typical input current harmonic values with variation of the output power
Load percentage
20 %
40 %
60 %
80 %
100 %
120 %
0 %
0.97
12 %
0.968
11 %
0.966
10 %
0.964
0.962
8 %
0.96
7 %
0.958
6 %
P
ow
er f
ac
to
r
THD
9 %
Figure 3.21:
Power Factor (PF) and THD (I) with variation of the output power. 12-pulse rectifier
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...