Installation and Connection
3-42 | CFW-11W G2
3
Table 3.24:
Content of parameter P0029
Bits
15
14
13
12
11 10
9
8
7
6
5
4
3
2
1
0
1
1
0
0
0
1
0
= inverter without safety
stop option
1
= inverter with safety
stop option
0
Inverter voltage:
01
= 380..480 V
10
= 500..600 V
11
= 500..690 V
or 660/690 V
Rated output current of the inverter
Hexadecimal digit #4 Hexadecimal digit #3
Hexadecimal digit #2
Hexadecimal digit #1
3.3.1 Installation
NOTE!
The inverter must be installed inside an IP54 panel (at least).
Table 3.25:
Signals from the terminals XC25 (terminals for Safety Stop)
Connector XC25
Function
Specifications
1
STO1
Terminal 1 of the coil of relay 1
Coil rated voltage: 24 V, range from 20 to 30 Vdc
Coil resistance: 960 Ω ±10 % @ 20 °C (68°F)
2
GND1
Terminal 2 of the coil of relay 1
3
STO2
Terminal 1 of the coil of relay 2
Coil rated voltage: 24 V, range from 20 to 30 Vdc
Coil resistance: 960 Ω ±10 % @ 20 °C (68°F)
4
GND2
Terminal 2 of the coil of relay 2
NOTE!
Follow the recommendations of
Item 3.2.12 Control Connections on page 3-29
.
For control cabling XC25 consider:
Use gauge from 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG) and maximum tightening torque of 0.50 N.m (4.50 lbf.in).
Use shielded cables connected to the ground on the inverter side only. Use the metal parts supplied as shown
in
The cables must run separately from the other circuits (power, control 110 V / 220 Vac, etc.).
3.3.2 Operation
3.3.2.1 Real Table
Table 3.26:
Operation of the Safety Stop function
Logical Level STO1 (voltage
between terminals XC25:1-2)
Logical Level STO2 (voltage
between terminals XC25:3-4)
Safety Stop
Function
Inverter Behavior
0 (0 V)
0 (0 V)
Activated
(enabled)
The inverter remains in the STO state and does
not accept commands. To leave such condition,
it is necessary to have STO1 = 1 and STO2 = 1
simultaneously
0 (0 V)
1 (24 V)
Fault
The inverter is tripped by fault F160 (fault related
to the Safety Stop). To leave this condition, it is
necessary to reset the inverter
1 (24 V)
0 (0 V)
1 (24 V)
1 (24 V)
Disabled
The inverter accepts commands normally
NOTE!
Maximum delay between signals STO1 and STO2: 100 ms (otherwise, fault F160 will occur).
The Safety Stop function has priority over the other functions of the inverter.
This function must not be used as control to start and/stop the inverter.
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...