Technical Data
CFW-11W G2 | 8-1
8
8 TECHNICAL DATA
This chapter contains the technical data (electrical and mechanical) of the CFW11W G2.
8.1 POWER DATA
Power supply:
The maximum rated line voltage of 690 V for models with DC power supply of 758...1150 Vdc, for altitude up
to 2000 m. For higher altitudes, the rated line voltage derating will be 1.1 % for each 100 m above 2000 m –
maximum altitude: 4000 m.
Frequency: 50/60 Hz (48 Hz to 62 Hz).
Phase imbalance: ≤ 3 % of the rated phase-phase input voltage.
Overvoltages according to Category III (EN 61010/UL 508C).
Transient voltages according to Category III.
Maximum of 12 connections per hour (1 every 5 minutes).
Typical efficiency: ≥ 98 %.
NOTE!
The power supply data assumes that the inverter is fed by a diode rectifier bridge.
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...