Troubleshooting and Maintenance
6-2 | CFW-11W G2
6
6.2 ALARMS, FAULTS AND POSSIBLE CAUSES
Table 6.1:
Alarms, faults and possible causes
Fault/Alarm
Description
Possible Causes
F020:
24 Vdc Power Supply
Undervoltage
Undervoltage on the 24 Vdc power supply that feeds
the control.
Voltage on the power supply below 22.8 Vdc.
F021:
DC Link Undervoltage
Undervoltage on the intermediate circuit.
Supply voltage too low, producing voltage on the
DC link below the minimum value (read value in
parameter P0004):
− Ud < 530 V – Supply voltage 500-525 V
(P0296 = 5).
− Ud < 696 V – Supply voltage 550-575 V
(P0296 = 6).
− Ud < 605 V - Supply voltage 600 V (P0296 = 7).
− Ud < 696 V – Supply voltage 660-690 V
(P0296 = 8).
Phase loss in the input.
Fault on the pre-charge circuit.
Parameter P0296 selected for use above the rated
line voltage.
F022:
DC Link Overvoltage
Overvoltage on the intermediate circuit.
Supply voltage too high, producing voltage on the
DC link above the maximum value:
− Ud > 1000 V - Models 500-600 V (P0296 = 5,
6 and 7).
− Ud > 1200 V - Models 660-690 V (P0296 = 8).
Driven load inertia too high or deceleration ramp
too fast.
Setting of P0151 or P0153 or P0185 too high.
F030:
(1)
Arm U Fault
Desaturation on the IGBTs of arm U.
Short circuit between phases U and V or U and
W of the motor.
F034:
(1)
Arm V Fault
Desaturation on the IGBTs of arm V.
Short circuit between phases V and U or V and
W of the motor.
F038:
(1)
Arm W Fault
Desaturation on the IGBTs of arm W.
Short circuit between phases W and U or W and
V of the motor.
A046:
High Load on the Motor
Motor overload alarm.
Note:
- It can be disabled by setting P0348 = 0 or 2.
Setting of P0156, P0157 and P0158 too low for
the motor.
Overload on the motor shaft.
A047:
Overload on the IGBTs
IGBT overload alarm.
Note:
- It may be disabled by setting P0350 = 0 or 2.
High current in the inverter output.
F048:
Overload on the IGBTs
IGBT overload fault
Current in the inverter output too high.
F067:
Encoder /Motor Wiring Is
Inverted
Fault linked to the phase relation of the encoder
signals, if P0202 = 4 and P0408 = 2, 3 or 4.
Note:
- This error can only occur during self-tuning.
- This fault cannot be reset.
- In this case, de-energize the inverter, solve the
problem and then energize it.
U, V, W wiring to the motor is inverted.
Encoder channels A and B are inverted.
Error in the encoder assembly position.
F070:
Overcurrent/
Short circuit
Overcurrent or short circuit in the output, DC link or
braking resistor.
Short circuit between two motor phases.
Short circuit of the connecting cables of the
dynamic braking.
F071:
Overcurrent in the Output
Output overcurrent fault.
Load inertia too high or acceleration ramp too
fast.
Setting of P0135 or P0169, P0170, P0171 and
P0172 too high.
F072:
Motor Overload
Motor overload fault.
Note:
- It can be disabled by setting P0348 = 0 or 3.
Setting of P156, P157 and P158 too low for the
motor.
Load on the motor shaft is too high.
F074:
Ground Fault
Ground overcurrent fault.
Note:
- It may be disabled by setting P0343 = 0.
Short circuit to the ground in one or more output
phases.
Motor cable capacitance too high, causing
current peaks in the output.
(4)
F076:
Motor Current Unbalance
Motor current imbalance fault.
Note:
- It may be disabled by setting P0342 = 0.
Poor contact or interrupted wiring in the
connection between the inverter and the motor.
Vector control with orientation loss.
Vector control with encoder, wiring of the encoder
or connection to the motor inverted.
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...