Energization and Start-Up
5-2 | CFW-11W G2
5
15. Mechanically uncouple the motor from the load.
If the motor cannot be uncoupled, make sure that any speed direction (forward or reverse) will not result in
personnel injury and/or equipment damage.
16. Command the drive, pre-charge the link and close the main circuit breaker/contactor.
17. Check the success of the energization.
18. The display must show the standard monitoring screen (
(a)), the status LED must
turn on and remain on in green.
5.2 START-UP
The start-up in the V/f mode is simply explained in three steps, using the programming facilities with the existing
parameter groups
Oriented Start-Up
and
Basic Application
.
Sequence:
1. Set the password to change parameters.
2. Execution of the
Oriented Start-Up
routine.
3. Setting the parameters of the
Basic Application
group.
5.2.1 Password Setting in P0000
Step
Action/Result
Display Indication
Step
Action/Result
Display Indication
1
- Monitoring mode
- Press
"Menu"
(rigth soft
key)
Ready
LOC
0rpm
15:45
Menu
0
rpm
0.0
A
0.0
Hz
5
- When number
5
is
displayed in the keypad,
press
"Save"
Ready
LOC
0rpm
Return
15:45
Save
P0000
Access to Parameters
5
2
- Group
"00 ALL
PARAMETERS"
is already
selected
- Press
"Select"
Ready
LOC
0rpm
Return
15:45 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
6
- If the setting has been
properly performed, the
keypad should display
"Access to Parameters
P0000: 5"
- Press
"Return"
(left soft
key)
Ready
LOC
0rpm
Return
15:45 Select
Access to Parameters
P0000: 5
Speed Reference
P0001: 90 rpm
3
- Parameter
"Access to
Parameters P0000: 0"
is
already selected
- Press
"Select"
Ready
LOC
0rpm
Return
15:45 Select
Access to Parameters
P0000: 0
Speed Reference
P0001: 90 rpm
7
- Press
"Return"
Ready
LOC
0rpm
Return
15:45 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
4
- To set the password, press
the Up Arrow
until
number
5
is displayed in the
keypad
Ready
LOC
0rpm
Return
15:45
Save
P0000
Access to Parameters
0
8
- The display returns to the
monitoring mode
Ready
LOC
0rpm
15:45
Menu
0
rpm
0.0
A
0.0
Hz
Figure 5.1:
Sequence for allowing parameter change via P0000
Содержание CFW-11W G2 RB Series
Страница 13: ...General Information 2 6 CFW 11W G2 2 Figure 2 2 Power unit UP11W G2 Figure 2 3 Control unit UC11 G2...
Страница 63: ...Installation and Connection 3 46 CFW 11W G2 3 3 3 3 3 Certification www fs products com...
Страница 83: ...Energization and Start Up 5 14 CFW 11W G2 5...
Страница 99: ...Optional Items and Accessories 7 4 CFW 11W G2 7...