Installation and Connection
CFW-11W G2 | 3-9
3
3.1.6 Cooling System
shows the details of the coolant inlet and outlet.
Coolant inlet
Coolant outlet
Figure 3.14:
Detail of the coolant inlet and outlet
contains detailed specifications of the UP11W G2 cooling system.
Table 3.3:
Cooling system specifications
Coolant Inlet Temperature
From 0 ºC to 45 ºC (32 °F to 113 °F) according to the coolant; see
. From 45 ºC to 55 ºC (113 °F to 131 °F) with output current derating
Fluid Temperature Increase
(1)
6 °C (43 °F)
Coolant Flow
20 l/min
Maximum Flow Allowed
30 l/min
Maximum System Pressure in Relation to
the Atmosphere
6 bar (600 kPa)
Load Loss on the Inverter Heatsink
(1)
0,84 bar (84 kPa)
Coolant Inlet and Outlet Fittings Used on
the Inverter
Stainless steel bulkhead fitting for 16 mm tube, M24X1.5 thread and 24° taper (DIN
3861/ISO 8434-1). According to
Note:
1. Considering the 20 l/min flow and the composition of 88,5 % of water, 10 % de glycol and 1,5 % of inhibitor
CorteC VpCI-649 in the coolant.
M24X1.5 thread
Tube Gauge 16 mm
Internal taper of 24°
(DIN 3861 / ISO 8434-1)
Figure 3.15:
Details of the hydraulic connection on the product