WAGO I/O System 750 XTR
Device Description 31
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Pos: 54 /Alle Serien (Allgemeine Module)/Überschriften/Ebene 2/Normen und Richtlinien - Überschrift 2 @ 4\mod_1242804031875_21.docx @ 33646 @ 2 @ 1
3.8
Standards and Guidelines
Pos: 55 /Serie 750 (WAGO I/O SYSTEM)/Gerätebeschreibung (alte Struktur)/Zulassungen/Information: Weitere Informationen zu Zulassungen 750-xxxx @ 3\mod_1227190967156_21.docx @ 25221 @ @ 1
More information about approvals.
Detailed references to the approvals are listed in the document “
Overview on
WAGO-I/O-SYSTEM 750 approvals
”, which you can find via the internet under:
DOWNLOADS
Documentation
System Description.
Pos: 56.1 /Serie 750 (WAGO I/O SYSTEM)/Gerätebeschreibung (alte Struktur)/Normen und Richtlinien/Normen und Richtlinien I/O-Modul 750-xxxx, ohne Variantenangabe - Einleitung @ 7\mod_1274278887584_21.docx @ 56645 @ @ 1
750-495/040-010 I/O modules meet the following standards and guidelines:
Pos: 56.2 /Serie 750 (WAGO I/O SYSTEM)/Gerätebeschreibung (alte Struktur)/Normen und Richtlinien/Normen und Richtlinien XTR - Mechanik und Klima Komponenten-HB 2017 - ohne Schiffbau @ 37\mod_1600765100003_21.docx @ 594045 @ @ 1
Table 19: Climatic and Mechanical Environmental Conditions and Shipbuilding
Standard
Test Value
Transport
EN 60870-2-2
Ct2(2k4) (except precipitation/water/moisture)
Mechanical Environmental Conditions
EN 61850-3
Achieved
EN 60870-2-2
Bm
EN 60721-3-1
1M3
EN 60721-3-3
3M5
EN 60068-2-6
Acceleration 5g
IEC 60068-2-27 Shock
15g, 11 ms, 1000 shocks per axis and
direction, half-sine
25g, 6 ms, 1000 shocks per axis and direction,
half-sine
Environmental Requirements
EN 61850-3
Achieved
EN 60721-3-1
1K5 (except precipitation and ice formation)
EN 60721-3-3
3K7 (except wind-driven precipitation, water
and ice formation)
EN 60870-2-2
C3 (except wind-driven precipitation and ice
formation)
Pos: 56.3 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1