WAGO I/O System 750 XTR
Appendix 125
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Table 73: Parameter 40 (Supported by Firmware Versions 05 and above)
Parameter 40 – NOLOAD Threshold, Active Energy
Function
Data Type Access
Factory Setting
Active power threshold above which the active
power is metered
UINT
R/W
0x0000 (disabled)
0:
The NOLOAD threshold is disabled (factory setting)
1 … 30000:
Resolution: 0.001 % / LSB (0.001 % to 30.000 %)
The threshold is specified as a % of the full scale of the active power
P
fullscale
= 3,464,102 W
> 30000:
-reserved-
Table 74: Parameter 41 (Supported by Firmware Versions 05 and above)
Parameter 41 – NOLOAD Threshold, Reactive Energy
Function
Data Type Access
Factory Setting
Reactive power threshold above which the
active power is metered
UINT
R/W
0x0000 (disabled)
0:
The NOLOAD threshold is disabled (factory setting)
1 … 30000:
Resolution: 0.001 % / LSB (0.001 % to 30.000 %)
The threshold is specified as a % of the full scale of the reactive power
Q
fullscale
= 3,464,102 VAR
> 30000:
-reserved-
Table 75: Parameter 42 (Supported by Firmware Versions 05 and above)
Parameter 42 – NOLOAD Threshold, Apparent Energy
Function
Data Type Access
Factory Setting
Apparent power threshold above which the
active power is metered
UINT
R/W
0x0000 (disabled)
0:
The NOLOAD threshold is disabled
1 … 30000:
Resolution: 0.001 % / LSB (0.001 % to 30.000 %)
The threshold is specified as a % of the full scale of the apparent power
S
fullscale
= 3,464,102 VA
> 30000:
-reserved-