WAGO I/O System 750 XTR
Device Description 33
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Table 20: EMC – Immunity to Interference
Standard
Test Value
Alternating Components of the Voltage to DC Line Connections
• EN 61000-4-17
• EN 60255-26
15 %
Damped Oscillatory Waves
• EN 61000-4-18
• EN 60255-26
• IEEE C37.90.1
1.25 kV conductor/conductor
2.5 kV conductor/ground
Voltage Dips, Short-term Interruptions and Voltage Fluctuations to DC Supply
Inputs
• EN 61000-4-29
• EN 60255-26
Standard not applicable
Harmonics
• Shipbuilding*)
Max. 2 W
DC: 3 V
eff
,
AC: 10
% to 15th harmonic
10
% … 1
% for 15th to 100th harmonic
1
% for 100th to 200th harmonic
*) The list of ship certifications issued is available in the section “Approvals”.