750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Table 38: Register 43
Register 43 – Observation Interval, Peak Value Measurement, Phase 1
Function
Data Type Access
Factory Setting
Observation interval, peak value measurement,
phase 1
UINT
R/W
0x000A
0 … 5:
-not permitted-
6 … 254: Number of half waves for measuring peak values
≥ 255:
-not permitted-
Table 39: Register 44
Register 44 – Observation Interval, Peak Value Measurement, Phase 2
Function
Data Type Access
Factory Setting
Observation interval, peak value measurement,
phase 2
UINT
R/W
0x000A
0 … 5:
-not permitted-
6 … 254: Number of half waves for measuring peak values
≥ 255:
-not permitted-
Table 40: Register 45
Register 45 – Observation Interval, Peak Value Measurement, Phase 3
Function
Data Type Access
Factory Setting
Observation interval, peak value measurement,
phase 3
UINT
R/W
0x000A
0 … 5:
-not permitted-
6 … 254: Number of half waves for measuring peak values
≥ 255:
-not permitted-
Table 41: Register 46
Register 46 – Storage Interval, Energy Consumption
Function
Data Type Access
Factory Setting
Storing interval, energy consumption,
Resolution: 1 second
UINT
R/W
0x003C (60s)
0 … 59:
-not permitted-
60 … 255: Time in seconds up to automatic storage of energy values
≥ 256:
-not permitted-