52 Process Image
WAGO I/O System 750 XTR
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Expanded status word 1
Byte 2
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
STAT7 STAT6 STAT5
STAT4
STAT3
STAT2 STAT1
-
STAT7
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Threshold value, undervoltage, Lx:
0 = threshold value not reached
1 = threshold value underrun
If STAT_SEL = status of I/O module:
- No significance
STAT6
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Threshold value, overvoltage, Lx:
0 = threshold value not reached
1 = threshold value reached or exceeded
If STAT_SEL = status of I/O module:
- Rotary field indicator
0 = rotary field correct: L1-L2-L3, clockwise
1 = rotary field not correct, counterclockwise
STAT5
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Threshold value, overcurrent, Lx:
0 = threshold value not reached
1 = threshold value reached or exceeded
If STAT_SEL = status of I/O module:
- No significance
STAT4
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Status, zero crossings:
0 = signal zero crossings at phase Lx
1 = no zero crossings at phase Lx
If STAT_SEL = status of I/O module:
- No significance
STAT3
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Clipping of voltage signal at Lx:
0 = OK
1 = the voltage signal is outside the measurable
range of the I/O module and has been
limited (clipped).
If STAT_SEL = status of I/O module:
- No significance
STAT2
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Clipping of current signal at Lx:
0 = OK
1 = the current signal is outside the measurable
range of the I/O module and has been
limited (clipped).
If STAT_SEL = status of I/O module:
- No significance