WAGO I/O System 750 XTR
Device Description 27
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Table 12: Technical Data – Measured Values
Fundamental vibration/upper harmonic
Current 240 ms
Voltage 240 ms
HD/THD, current 240 ms
HD/THD, voltage 240 ms
Initialization times:
Collection changes
Collection 010 approx. 1400 ms
Collections 020, 021 and 022 approx. 1100 ms
Settling times:
Voltages and currents
3)
620 ms at 100
%
(1300 ms after power-on)
Active power and apparent power
2)
415 ms at 60 %
915 ms at 100 %
Reactive power
2)
715 ms at 60 %
1215 ms at 100 %
Harmonic Analysis
790 ms
Do not also ground sensors on the module
All sensors are internally connected to PE on one side (N) and must therefore not
be grounded on the module side, as otherwise ground loops can form.
Signal line shielding must be grounded on one side on the side of the sensors.
3
The settling time is the time in which the measured value has increased from 0 to the value specified in percent
of the full scale.