34 Device Description
WAGO I/O System 750 XTR
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Table 21: EMC – Emission of Interference
Standard
Test Value
*)
Enclosure Emission of Interference
• EN 61000-6-3
• EN 55032 Class B
30 dB(µV/m), QP, 30 MHz … 230 MHz
37 dB(µV/m), QP, 230 MHz … 1 GHz
70 dB(µV/m), Peak, 1 GHz … 3 GHz
50 dB(µV/m), AV, 1 GHz … 3 GHz
74 dB(µV/m), Peak, 3 GHz … 6 GHz
54 dB(µV/m), AV, 3 GHz … 6 GHz
• EN 61000-6-4
• EN 60255-26
• EN 55011 Class A
• EN 55032 Class A
40 dB(µV/m), QP, 30 MHz … 230 MHz
47 dB(µV/m), QP, 230 MHz … 1 GHz
76 dB(µV/m), Peak, 1 GHz … 3 GHz
56 dB(µV/m), AV, 1 GHz … 3 GHz
80 dB(µV/m), Peak, 3 GHz … 6 GHz
60 dB(µV/m), AV, 3 GHz … 6 GHz
Conducted Emission of Interference – Line Connection AC Voltage
• EN 61000-6-3
• EN 55032 Class B
Standard not applicable
• EN 61000-6-4
• EN 55011 Class A
• EN 50121-3-2
Standard not applicable
Conducted Emission of Interference – Line Connection DC Voltage
• EN 61000-6-3
• EN 60255-26
• EN 55032 Class A
79 dB(µV) QP, 0.15 MHz … 0.5 MHz
66 dB(µV) AV, 0.15 MHz … 0.5 MHz
73 dB(µV) QP, 0.5 MHz … 30 MHz
60 dB(µV) AV, 0.5 MHz … 30 MHz
*)
QP = Quasi Peak Detector; AV = Average Detector
**)
If necessary, please find different data in the section “Approval” (regarding approval for
EMC A or EMC B).