92 Commissioning
WAGO I/O System 750 XTR
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
8.2.3
“Energy” Tab
On the “Energy” tab, you can adjust or reset the energy values for each phase
after entering the password.
The initial password is “wago”. After the first use, please change this password
using [
Change password
].
If you have forgotten the password, you can uninstall and reinstall the plug-in for
the 3-Phase Power Measurement Module. This resets the password to the initial
password.
•
The I/O module counts the
Energy consumption
and saves the values
cyclically. However, with the [
Save
] and [
Delete
] commands, you can save
the energy consumption prematurely or reset it to 0.
•
You can also set the
Energy meters
to a particular value, i.e. pre-populate
them, by selecting the meter in question in the list field, entering a value in
milliwatt hours and clicking [
Save
]. After this is set, the energy metering
starts from this value setting. 15 meters can be selected:
Active energy import, Lx; Active energy export, Lx; Reactive energy,
inductive, Lx; Reactive energy, capacitive, Lx; and Apparent energy, Lx.
See also: tab 4 in “Appendix” > “Tab Assignment.”
The following sum meters cannot be selected: Active energy, Lx; Active
energy, total; Active energy import, total; Active energy export, total;
Reactive energy, total; Reactive energy, inductive, total; Reactive energy,
capacitive, total; and Reactive energy, Lx. To pre-populate or delete these,
you must select and set the individual components. For example, for active
energy, L1, these would be: Active energy import, L1 and Active energy
export, L1.
These actions are performed immediately and cannot be reverted. Therefore, the
[
Save
] button at the bottom of the window is disabled.