USER PROGRAMMABLE INPUT 

(Thermocouple types J, K, T, & E, or millivolt)

  

MICROPROCESSOR CONTROLLED

  

SIMPLE ADJUSTABLE RANGE SETTING (Using Input Signal)

  

THERMOCOUPLE BREAK DETECTION

  

MOUNTS ON “T” AND “G” STYLE DIN RAILS

  

3-WAY ELECTRICAL ISOLATION (POWER/INPUT/OUTPUT)

  

MULTIPLE ANALOG OUTPUTS (0 to 20 mA, 4 to 20 mA, and 0 to 

10 VDC)

  

WIDE OPERATING TEMPERATURE RANGE (-25°C to 75°C)

  

POWER & MEMORY ERROR INDICATION

  

9 to 32 VDC POWERED

DESCRIPTION

The ITMA accepts a thermocouple or millivolt input and converts it into a 

voltage or current output. The voltage or current output is linearly proportional 

to the temperature or millivolt input. This output is ideal for interfacing to 

indicators, chart recorders, controllers, or other instrumentation equipment. 

The ITMA is DC powered. The DC power input is isolated from the signal 

input and analog output. The unit scales the analog output proportionally to the 

thermocouple or millivolt input signal. The analog output may be configured for 

one of the following: 0 to 20 mA, 4 to 20 mA, or 0 to 10 VDC. Making the 

signal conversion with the ITMA to a current output signal, makes the signal 

less susceptible to noise interference and allows accurate transmission over long 

distances. The 3-Way isolation allows the use of grounded thermocouples which 

can provide additional noise reduction benefits.

The ITMA uses a ten position DIP switch to accomplish the input sensor 

configuration, range selection, and unit calibration. A simple range setting 

technique (Field Calibration) is used so the actual input signal adjusts the output 

for scaling. This technique eliminates the need for potentiometers which are 

vulnerable to changes due to vibration.

The unit is equipped with a universal mounting foot for attachment to 

standard DIN style mounting rails, including top hat rail (T) according to EN 50 

022 - 35 

×

 7.5 and 35 

×

 15, and (G) profile according to EN 50 035 - G 32.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the 

manual or on equipment must be observed to ensure personal safety and to 

prevent damage to either the instrument or equipment connected to it. If 

equipment is used in a manner not specified by the manufacturer, the protection 

provided by the equipment may be impaired.

SPECIFICATIONS

1.

 POWER

: 9 to 32 VDC; 1.75 W The power supply must have 300 mA for 200 

msec. surge capacity.

2.

 INPUT

: J, K, T, E, mV [selectable via DIP switch]

3. 

OUTPUT

: Self-powered (active); All output signals scaled linearly using 

temperature or mV input. Unit is shipped set for 4 to 20 mA output. 4 to 20 

mA or 0 to 20 mA selected via internal jumper.

Voltage Output Compliance

:

0 to 10 VDC across min 1 K

 load (10 mA)

20 mV peak to peak max. ripple (for frequencies up to 120 Hz)

Current Output Compliance

:

0 to 20 mA through max. 600

 load (12 VDC)

4 to 20 mA through max. 600

 load (12 VDC)

15 mV peak to peak max. ripple across 600

 load (for freq. up to 120 Hz)

4.

 TC BREAK DETECTION

: Nominal values shown in the following order: 

(0 to 20 mA, 4 to 20 mA, and 0 to 10 VDC).

Upscale

: 22.9 mA, 22.5 mA, and 11.5 VDC

Downscale

: -0.5 mA, 3.5 mA, and -0.4 VDC

5.

 RESPONSE TIME

: 400 msec (to within 99% of final value w/step input; 

typically, response is limited to response time of probe.)

6.

 TEMPERATURE EFFECTS

:

Temperature Coefficient

:  

±

 0.025% of input range per °C

Ice Point Compensation

:  

±

 0.75°C for a 50°C change in temperature

7.

 DIELECTRIC WITHSTAND VOLTAGE

: 1500 VAC for 1 minute

Working Voltage

: 50 VAC

Power input to Signal input, Power input to Signal output, & Signal input to 

Signal output.

8.

 RANGE & ACCURACY

: (12 Bit resolution)

Accuracy

±

 ( 0.075% Range + 0.25°C [Conformity] + 0.50°C [Ice Point]) 

at 23°C after 20 min. warm-up, conforming to ITS-90.

Note: TC Conformity and Ice Point do not apply to mV input

MODEL ITMA DC - 

INTELLIGENT THERMOCOUPLE MODULE WITH ANALOG

 

OUTPUT

4.20 RE

F

1.08

3.12

(27.5)

(106.7

)

(79.2)

ERROR

POWER

ITMA

OUTPUT CA

L

FIELD CA

L

BASIC CA

L

ICE PT DIS/EN

OPEN SEN UP/D

N

RANG

E

RANG

E

DIP SWITCH SETTINGS

:

ON = 

1

OFF = 

0

MC2220X

8

9

10

TC TYPE

TC TYPE

TC TYPE

4

5

6

7

3

2

1

UP

1

7

0

0

1

1

1

1

2

3

1

RANG

E

0

1

9

0

0

0

K

T

MV E

0

0

1

TC TYPE

J

6

0

0

1

10

0

1

1

0

1

1

8

0

SWITCH

4

0

1

5

0

DISABLE

D

OPEN SE

N

DOWN

ICE POIN

T

ENABLE

D

9-32 VD

C

ERRO

R

POWE

R

VDC+

10

TC
+

7

V+

4

I+

1

VDC-

TC
-

12

11

9

8

6

5

V-

3

2I

-

RED LION CONTROLS

MADE IN U.S.A.

YORK, PA

.

MODEL ITMA

 DIMENSIONS  In inches (mm)

CAUTION: Read complete instructions prior 

to installation and operation of the unit.

Bulletin No.  ITMA3-D
Drawing No.  LP0405
Released  06/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

Содержание ITMA

Страница 1: ...ment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired SPECIFICATIONS 1 POWER 9 to 32 VDC 1 75 W The power supply must have 300 mA for 200...

Страница 2: ...rols and heaters etc The cables should be run through metal conduit that is properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used i...

Страница 3: ...e case and cut the wire jumper The jumper is located to the left side of the board as shown in the drawing POWER Connect DC power to terminals 10 and 12 observing proper polarity Be certain DC power i...

Страница 4: ...en turn on power and the previous settings will be loaded Field Calibration with a Thermocouple Calibrator 1 1 Enable the Ice Point Compensation on the Thermocouple Calibrator and set it to the Thermo...

Страница 5: ...Output increases to 0 8 mA 3 5 mA or 0 4 V nominal or more 4 19 Perform a Field Calibration See Section 1 0 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 1...

Страница 6: ...S POWER SUPPLY 24VDC COMM MASTER CONTROL ROOM G Rail Installation To install the ITMA on a G style DIN rail angle the module so that the upper groove of the foot catches under the lip of the top rail...

Страница 7: ...7 This page intentionally left blank...

Страница 8: ...Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any p...

Отзывы: