background image

3

WIRING CONNECTIONS

All conductors should meet 

voltage and current ratings for each 

terminal. Also, cabling should 

conform to appropriate standards of 

good installation, local codes and 

regulations. It is recommended that 

power supplied to the unit be 

protected by a fuse or circuit 

breaker. When wiring the unit, use 

the numbers on the label to identify 

the position number with the proper 

function. Strip the wire, leaving 

approximately 1/4" (6 mm) of bare 

wire exposed (stranded wire should 

be tinned with solder). Insert the 

wire into the terminal, and tighten 

the screw until the wire is clamped 

tightly.

INPUT, OUTPUT, AND POWER CONNECTIONS

INPUT

Ensure thermocouple wire ends are stripped and clean. Connect positive 

thermocouple lead to terminal #7 (TC+). Connect negative thermocouple lead 

to terminal #8 (TC-). If the thermocouple probe cannot be connected directly to 

the module, thermocouple wire or thermocouple extension-grade wire must be 

used to extend the connection (copper wire does not work). Always refer to the 

thermocouple manufacturer’s recommendations for: mounting, temperature 

range, shielding, etc.

OUTPUT 

Connect the output signal wires to the desired output terminals. For voltage 

output, use terminals #4 and #6; for current output, use terminals #1 and #3 

observing proper polarity. Only one output may be used at a time. The unit is 

factory set for a 4 to 20 mA output. The voltage output will track the current 

output nominally within a ±2.5% deviation range.

To select 0 to 20 mA, output you must open the case and cut the wire jumper. 

The jumper is located to the left side of the board as shown in the drawing.

POWER 

Connect DC power to terminals #10 and #12 observing proper polarity. Be 

certain DC power is within the 9 to 32 VDC specifications.

POWER LED

The ITMA has a green LED located on the front to indicate that power is 

applied to the unit.

DIP SWITCH SETTING DESCRIPTIONS

TC Type and Range switch settings (ON = 1  OFF = 0)

FACTORY SETTINGS

The unit is shipped from the factory calibrated for a 4 to 20 mA output using 

a type J thermocouple in range 3. The ITMA should be Field calibrated by the 

operator for the application environment it will be used in. If the unit is not 

recalibrated by the operator, the following table lists the temperature ranges for 

the given thermocouple types.

TROUBLESHOOTING

For further technical assistance, contact technical support at the appropriate 

company numbers listed.

SWITCH

LABEL

DESCRIPTION

1

OUTPUT CAL Output Calibration

2

FIELD CAL Field Calibration

3

BASIC CAL Basic Calibration

4

ICE PT DIS/EN Ice Point Compensation -  

Disabled (ON) / Enabled (OFF)

5

OPEN SEN UP/DN Open Sensor Detection -  

Upscale (ON) / Downscale (OFF)

6
7
8

TC TYPE Thermocouple Type - 3 switch 

combination setting

9

10

RANGE Sensor Range - 2 switch 

combination setting

mV

1

1

DIP SWITCH

TC 

TYPE

6

8

7

J

0

0

0

K

0

1

0

T

0

0

1

E

0

1

1

DIP SWITCH

RANGE

9

10

0

0

0

1

1

0

1

2

1

0

3

1

1

TYPE

T

J

RANGE

3

3

NOMINAL FACTORY FIELD CALIBRATION

TEMPERATURE RANGE

-195°C to 162°C

-50°C to 500°C

E

K

3

3

3°C to 602°C

-85°C to 790°C

Remove this 

side of the 

unit case.

WIRE JUMPER

ERROR

POWER

VDC+

10

TC+

7

V+

4

I+

1

VDC-

TC-

12

11

9

8

6

5

V-

3

2

I-

POWER SUPPLY

9 to 32 VDC

+

-

VOLTAGE METER

OR

CURRENT METER

MONITORING   INSTRUMENT

Содержание ITMA

Страница 1: ...ment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired SPECIFICATIONS 1 POWER 9 to 32 VDC 1 75 W The power supply must have 300 mA for 200...

Страница 2: ...rols and heaters etc The cables should be run through metal conduit that is properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used i...

Страница 3: ...e case and cut the wire jumper The jumper is located to the left side of the board as shown in the drawing POWER Connect DC power to terminals 10 and 12 observing proper polarity Be certain DC power i...

Страница 4: ...en turn on power and the previous settings will be loaded Field Calibration with a Thermocouple Calibrator 1 1 Enable the Ice Point Compensation on the Thermocouple Calibrator and set it to the Thermo...

Страница 5: ...Output increases to 0 8 mA 3 5 mA or 0 4 V nominal or more 4 19 Perform a Field Calibration See Section 1 0 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 1...

Страница 6: ...S POWER SUPPLY 24VDC COMM MASTER CONTROL ROOM G Rail Installation To install the ITMA on a G style DIN rail angle the module so that the upper groove of the foot catches under the lip of the top rail...

Страница 7: ...7 This page intentionally left blank...

Страница 8: ...Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any p...

Отзывы: